The ICAM IFT-4 and IFT-6 by Xtralis are aspirating smoke detection systems with an alarm sensitivity range from 0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft). These detectors are classified as Very Early Warning Smoke Detectors that can reliably detect fire at an early stage, and low to high concentrations of smoke over an area of 2,000 m2 (21,500 sq. ft.). The detectors are configurable for a variety of environments. Addressability provides more detail into fire location, enabling faster response.
4 and 6 zones
Large bore 4- and 6-pipe air sampling
0.001% to 20% obscuration/m (0.0003% to 6.10% obscuration/ft)
4 Alarms - Alert, Action, Fire 1, Fire 2
4 x 100 m (4 x 328 ft) and 6 x 100 m (6 x 328 ft.) sampling pipe
Enhanced performance aspirator
Ethernet TCP/IP
RS232 and RS485 Modbus
Up to 16 additional relay outputs available
Optional 4 to 20 mA analog outputs
Area coverage of up to 2000 m2 (21,500 sq. ft.)