PRODUCT DESCRIPTION & PRINCIPLE OF OPERATION
AutoFireX® DLP- Direct Low-Pressure Clean Agent Systems are primarily Pre-Engineered Automatic Fire detection and suppression Systems utilising various Low-pressure Clean agents like,HFC227ea, FK 5-1-12, FE36. These Units are designed, manufactured, and tested in ISO 9001:2015 certified facilities.
The AutoFireX® Linear Pneumatic Fire Detection Tubing (LP-FDT) is installed and connected to DLP Valve via dual seal threaded union attached to the isolation ball valve and routed throughout the protected hazard area/enclosure. Being heat sensitive, the primary function of Linear Pneumatic Fire Detection Tube (under pressure) is to detect heat/fire and activate the valve for discharge of the agent by rupturing at the hottest point along its installed length on flame impingement. On rupture a nozzle is formed at the burst point.
Due to loss of the pressure in the tube, the clean agent under pressure, in the cylinder then flows out through the tube and discharged out at burst point/nozzle, extinguishing the fire instantly and flooding the protected enclosure, which helps in preventing reignition.
Each DLP system consists of a High-Grade Stainless-Steel Direct valve with integrated pressure gauge adaptor with Schrader valve on the valve body to monitor cylinder pressure, and a quarter turn isolation valve to interface with the AutoFireX® Fire Detection Tubing., and a PRD (Pressure Relief Device) tested up to 44Bar is also provided. The systems is supplied complete with CE Cylinders and Brackets Stainless steel siphon tube with appropriate agents, as required.