Description

Overview
The ISOMETER® isoNAV685-D-B is an insulation monitoring device for offline monitoring of de-energised TN, TT or IT systems in accordance with IEC 61557-8. It provides measurement and trend recording of insulation resistance and supports remote access and network integration.

Key features
  • Offline monitoring of de-energised loads and systems
  • Monitors three insulation levels
  • AMPPLUS measurement method with automatic adaptation to system leakage capacitance
  • Adjustable response value 10 kΩ…1 MΩ (factory setting 50 kΩ)
  • Reduced measuring voltage for increased safety
  • High-resolution graphic LC display with isoGraph for trend visualisation
  • History memory with real-time clock (buffer for three days) storing up to 1023 timestamped alarm messages
  • Earth connection monitoring and automatic device self-test
  • Freely programmable digital inputs and outputs
  • Communication: Modbus TCP, BCOM, built-in web server; COMTRAXX® Gateway optional
  • Remote setting and worldwide remote diagnosis via Internet/Intranet


Applications
  • Monitoring of de-energised loads and networks in industrial electrical installations, switchgear and control panels


Variants
Type | Nominal system voltage range | Supply voltage | Art. No.
isoNAV685-D-B | offline | AC 24…240 V; 50…400 Hz / DC 24…240 V | B91067024

Optional accessories
  • Set of screw terminals — Art. No. B91067901
  • Set of push-wire terminals — Art. No. B91067902
  • Enclosure accessories (terminal cover, 2 mounting clips) — Art. No. B91067903


Technical specifications
  • Standard: IEC 61557-8 (insulation monitoring for IT systems)
  • Application: de-energised TN, TT or IT systems
  • Measurement method: AMPPLUS
  • Response value adjustable: 10 kΩ … 1 MΩ (factory 50 kΩ)
  • Display: High-resolution graphic LC display; isoGraph for trend representation
  • History memory: up to 1023 alarm messages with date/time (3-day buffer)
  • Digital I/Os: freely programmable
  • Remote access: Web server; option COMTRAXX® Gateway; worldwide remote diagnosis
  • Communication: BCOM, Modbus TCP
  • Measuring voltage: reduced measuring voltage
  • Supply voltage (example variant): AC 24…240 V; 50…400 Hz / DC 24…240 V
  • Article number (example variant): B91067024

Exhibitions

Meet this supplier at the following exhibition(s):

InnoTrans 2026
InnoTrans 2026

22-25 Sep 2026 Berlin (Germany) Hall 9 - Stand 350

  • More information
    SPS 2026
    SPS 2026

    24-26 Nov 2026 Nuremberg (Germany) Hall 4A - Stand 211

  • More information
    *Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.