Air filter Absolute™ 1D
panelfiberglassexhaust

air filter
air filter
Add to favorites
Compare this product
 

Characteristics

Designed for
air
Filtration element
panel, fiberglass
Applications
exhaust
Material
aluminum, aluminium, polyurethane
Norms
H13
Other characteristics
HEPA, high-capacity, rugged
Operating pressure

250 Pa
(0.036 psi)

Flow

Max.: 3,190 m³/h
(112,653.787 ft³/h)

Min.: 340 m³/h
(12,006.987 ft³/h)

Fluid temperature

110 °C
(230 °F)

Description

HEPA filter class H13 for supply- or exhaust air system, that require high mechanical strength. Applications with temperature above 70°C (maximum 110°C). Pleats are uniformly separated by corrugated aluminum separators incorporating a hemmed edge to prevent damage to the media. Low to medium airflows (up to 1,8 m/s) Very high mechanical strength Increased temperature resistance 100% leak-free : individually scan tested High dust holding capacity Application HEPA Filter for standard applications Frame Plywood Media Glass fiber Relative Humidity 100% Recommended final pressure drop 2x Initial pressure drop Separator Aluminium Gasket Polyurethane, endless foamed Sealant Polyurethane Installation options FKB, FKB/D, CamBox Comment Remarks: All filter tested acc. EN 1822. Other editions on request