Product DescriptionGasTDL-3001 is an in-situ extractive tunable diode laser absorption spectroscopy (TDLAS) gas analyzer for real-time measurement of NH3 and HCl in flue gas. The unit mounts directly on the stack and uses a heated, in-situ extractive sampling path to prevent adsorption and loss of acidic and ammonia species, ensuring representative samples and fast response. Full-path calibration capability secures long-term measurement accuracy for flue gas cleaning control and environmental emission monitoring in power generation, chemical and metallurgical industries.
Segment / DivisionSegment: Flue Gas Analyzer; Division: Continuous Emission Monitoring System (CEMS).
Applications- SCR/SNCR systems
- Coal-fired power plants
- Aluminium production
- Glass manufacturing
- Cement plants
- Fertilizer plants
- Waste incineration facilities
Features- Anti-interference measurement by TDLAS providing high selectivity against background gases
- Full-path calibration for sustained measurement accuracy
- Ultra-low detection limits via multi-pass optical cell
- Heated, low-adsorption gas path to prevent NH3 and HCl condensation and sample loss
- In-situ extractive sampling to minimize effects of dust, temperature and pressure fluctuations
- Compact design for flexible and easy installation
Specifications- Measurement components: NH3, HCl
- Measurement principle: Tunable Diode Laser Absorption Spectroscopy (TDLAS)
- Measurement range: NH3 0-10-100 ppm; HCl 0-20-100 ppm (customizable)
- Resolution: 0.01 ppm
- Precision: ±1% F.S.
- Response time: T90 ≤ 30 s
- Working temperature: -30 to +60 °C
- Power supply: 220V AC, 50Hz, 800W
- Backflush gas: 0.4–0.8 MPa clean, dry compressed air
- Heating temperature: 190 °C
- Communication: RS485, RS232
- Output: 4-20 mA, relay
- Cabinet protection level: IP65