Single and three phase protection
Phase failure (loss phase) protection
Phase sequence protection
Adjustable voltage protection
Over voltage and/or low voltage protection
Contact outputs for system control (OUT, OUT2)
Rail mounted, screw-terminal connections
CE marked according to European Norms
Environmental Conditions
Ambient/Storage Temperature - 0 ...+50 ºC / -25...+70 ºC
Relative Humidity - 80% relative humidity for temperatures up to 31°C, decreasing linearly to 50% at 40°C
Protection Degree - IP20, According to EN 60529
Height - Max. 2000m
Electrical Characteristics
Supply - 125-410V AC +10% -10%
Operating Frequency - 45-65 Hz
Power Consumption - Max. 10VA
External Connections - Screw-terminal connections
Reset Time - Max. 0.01s
Outputs
Control Output (OUT) - 250V AC, 10A (for resistive load), NO+NC
Control Output (OUT2) - 250V AC, 10A (for resistive load), NO+NC
Life Expectancy - Mechanical 10.000.000 operations (under no load), Electrical 50.000 operations (10A at 250V AC, resistive load)
Control Output State - Out LED control output (OUT) lits when device is powered
Out LED control output (OUT) lits when device is powered and phase sequence failed (during this state, OUT2 relay will switch On)
Housing
Mounting Method - TH35 rail mounting
Dimensions - W18xH84xD62 mm
Weight - Approx. 90g (after packaging)
Enclosure Material - Self extinguishing plastics