The general purpose vibration liquid level switch provides high or low liquid level detection of dirty liquids or those with light to medium coating or scaling characteristics with a 1A relay output. Media examples include wastewater, diluted caustic soda and copper sulfate. For optimum performance, the sensor automatically adjusts for coating build up, and if necessary, outputs a proactive maintenance alarm to request cleaning. The submersible PP-Ryton® level switch sensor is universally mounted through the tank wall or inside the tank, and connected to a PLC or relay controller.
FEATURES
Automatic coating adjustment optimizes sensor performance
Submersible Ryton® sensor with polypropylene cable for corrosive liquids
Maintenance alarm proactively alerts user if sensor cleaning is required
60VA SPST relay selectable NO or NC via power supply wiring polarity
Compatible with Smart Trak and Switch-Pak installation fittings
Orientation: Universal
Accuracy: ± 1mm in water
Repeatibility: ± 0.5mm in water
Supply voltage: 12-30 VDC
Consumption: 25 mA maximum
Contact type: (1) SPST relay
Contact rating: 60 VA, 1A maximum
Contact output: Selectable NO / NC
Maint. alarm: NPN transistor, 10 mA maximum
Sensor rating: NEMA 6 (IP68)
Sensor material: Ryton® (glass filled)
Grommet mat.: Viton®
Cable jack. mat.: Polypropylene
Cable type: 5-conductor, shielded, #24 AWG
Cable length: 10’ (3m)
Process mount: 3/4” NPT (3/4” G)
Mount. gasket: Viton®
Classification: General purpose
Compliance: CE