Smoke extraction motors are certified following the tests conducted according to the TS EN 12101-3 Standard. The tests were carried out in Applus + and Efectis Test Laboratory. As a result of the tests, Gamak Smoke Extraction Motors have been certified in conformance with 300°C 2 hours operation. They are used to create a smoke-free area so that extinguishing and rescue work can be done easily in case of fire, while preventing any damage to the living beings in the environment. Smoke extraction motors work in conjunction with jet fans for both emergencies during fire and ventilation needs in indoor areas. They are designed for S1 Continuous + S2 Short-term (Emergency) operation.
There are 2 types of motors used in these ventilators:
S2: Short-term EMERGENCY operation - Operation for a predetermined time and temperature in case of fire.
S1 + S2: Continuous operation + short term EMERGENCY operation - Continuous operation is for ventilation purposes, e.g. removal of exhaust gases in road tunnels.
In case of continuous operation request, smoke motors can be manufactured with high efficiency.
How long and at what temperature the motors will be operated in EMERGENCY operation must be specified in advance by the user.