GeneralThe low-voltage dynamic reactive power compensation cabinet DRPC-30–800 kvar provides fast, automatic reactive power compensation using a contactless switching system controlled by a dynamic compensation controller. It tracks rapid reactive current variations and switches capacitor banks quickly and frequently to maintain optimal power factor, reduce line losses and increase effective output of distribution transformers, improving overall power quality.
Service Conditions- Altitude: ≤ 2000 m
- Ambient temperature: -40°C ~ +45°C
- Relative humidity: ≤ 90%
- Environment: free of corrosive gases, conductive dust, flammable or explosive media
- Installation site: no severe vibration or shock; inclination ≤ 5°
StandardsIEC 439 — Low-voltage switchgear and controlgear equipment; IEC 144 — AC high-voltage contactor; GB3906; GB-11022; GB311.1–311.6; GB763; GB2706; GB7252.
Structural characteristics- Main components: air switches (or knife switches), capacitors, reactors, fuses (or small circuit breakers), contactless switches and dynamic controller; compact and optimized layout
- Panel instruments: controller, ammeter, voltmeter and signal lights for real-time monitoring
- Cabinet construction: cold-rolled steel plate (or stainless steel) with spray coating; internal framework in galvanized steel
- Protection functions: short-circuit, overload, over-voltage, under-voltage and phase-loss protection; automatic shutdown and resume on external fault
- Reactive rate options: 6%, 7%, 12%, 14%
Technical parameters- Rated voltage: 380 V, 660 V
- Rated frequency: 50 Hz / 60 Hz
- Rated compensation capacity: 30–800 kvar
- Operating voltage range: 0.8–1.1 Un
- Compensation methods: common compensation, split compensation, mixed compensation
- Measurement accuracy: Voltage ±0.5%; Current ±1.0%; Reactive power ±1.0%
- Maximum allowable overcurrent: 1.30 × rated current
- Control circuits: 1–16 circuits
Product Features- Fast switching: dynamic response time ≤ 20 ms; restart after group capacitor exit can complete within one cycle
- Effective compensation: closed-loop controller compensates according to system voltage and reactive power
- Comprehensive protection: over-voltage, under-voltage, short-circuit, phase-loss, temperature-limit protections
- Automatic operation: automatic exit on external faults or outages and automatic resume after power restoration
Ordering Notice- Specify transformer rated capacity, secondary-side rated voltage and CT transformation ratio
- Provide reactive load conditions, natural power factor, total operating current and fluctuation range of the compensated system
- State whether load is impact, fluctuating or steady-state
- Specify device model/type and total capacity required
- For outdoor units, indicate cabinet material (carbon steel or stainless steel) and color; list any special requirements
Technical specifications- Rated voltage: 380 V or 660 V
- Frequency: 50 Hz or 60 Hz
- Compensation capacity: 30–800 kvar
- Operating voltage range: 0.8–1.1 Un
- Dynamic response time: ≤ 20 ms
- Measurement accuracy: Voltage ±0.5%; Current ±1.0%; Reactive power ±1.0%
- Allowable overload: up to 1.30 × rated current
- Control circuits: 1–16
- Reactive rate options: 6%, 7%, 12%, 14%