GeneralThe shunt capacitor without external fuse is engineered to IEC and GB standards for reactive power compensation in three-phase AC systems. It features a compact modular arrangement for straightforward installation and maintenance.
PurposesUsed on three-phase AC networks ≥ 1 kV, 50 Hz, to improve system power factor, reduce network losses and stabilise voltage quality. Suitable for banked capacitor compensation and harmonic-mitigated installations when fitted with series reactors.
Service conditions- Installation: indoor (standard) or outdoor (option dependent).
- Altitude: ≤ 1,000 m (insulation correction required above 1,000 m).
- Ambient temperature: -5 °C to +50 °C.
- Environment: free from conductive/explosive dust, severe mechanical vibration and harmful gases/vapours.
Personal safetyCapacitors store charge and can retain residual voltage after de‑energisation. Before any intervention, capacitors must be properly grounded, short‑circuited and discharged. Do not touch both output terminals simultaneously. Decommissioned units must be short‑circuit grounded for an extended period prior to disassembly. Insulating oil is an eye irritant; avoid contact and rinse with clean water if contact occurs.
Structure- Typical composition: shunt capacitor bank; disconnector or earthing switch; ZnO surge arrester; discharge coil; optional current transformer for protection; confluence busbar; flexible copper interconnects; post/support insulators; modular steel frame.
Accessories functions- Disconnector/earthing switch: isolates and grounds the bank during maintenance; technical indices comply with relevant standards.
- Discharge coil: discharges the capacitor bank and provides measurement/relay signal source.
- ZnO surge arrester: provides switching and lightning over‑voltage protection; mounted close to the capacitor bank.
- Current transformer (when provided): supplies signal output for relay protection according to standards.
- Series reactor: reduces switching inrush, prevents instantaneous bus voltage drop and helps limit higher‑order harmonics impact (e.g. 3rd, 5th and above).
Technical specifications- Application: three‑phase AC systems, rated voltage ≥ 1 kV.
- Rated frequency: 50 Hz.
- Installation altitude: ≤ 1,000 m (insulation correction above 1,000 m).
- Ambient temperature range: -5 °C to +50 °C.
- Series reactor reactance options: ~0.5%–1%; ~5%–6%; or ~12%–13%.
- Maximum continuous operating current: up to 1.35 × rated current.
- Required reactance accuracy: ≥ 90% of rated reactance at maximum continuous current.
- Protections and components: discharge coil, ZnO arrester, optional CT for relay protection, disconnectors/earthing switches and modular bus arrangements.