Under-voltage protection relay PCS-985B/AW
under-frequencyover-excitationvoltage

Under-voltage protection relay - PCS-985B/AW - NR Electric - under-frequency / over-excitation / voltage
Under-voltage protection relay - PCS-985B/AW - NR Electric - under-frequency / over-excitation / voltage
Add to favorites
Compare this product

Characteristics

Measured/monitored value
under-voltage, under-frequency, over-excitation, voltage, frequency, current, over-voltage, over-frequency, excitation, under-excitation, overload, earth-leakage, over-current
Applications
for generators, for transformers, for turbines
Communication
Modbus
Norms
IEC
Other characteristics
with fault indication, reverse power, differential, digital, multifunction

Description

Product overview
PCS-985 generator-transformer unit protection can be applied for turbo-dynamo, gas-turbine, hydro, pumped storage and nuclear power generator with different connection modes. It supports conventional CT/VT and ECT/EVT, and provides interfaces for power plant automation.
For medium to large generator, two sets of PCS-985 protections can be used to achieve duplicated protection configuration. Two PCS-985 protections use different CT groups, and main and backup protection in one PCS-985 share one group of CTs.
PCS-985B provides complete protection scheme for a turbo-dynamo or nuclear power generator-transformer unit which usually comprises generator, main transformer, step-down transformer and exciter or excitation transformer.
PCS-985AW can be applied for large-scale hydro or pumped storage generator-transformer unit with different connection modes.

Current Differential Protection (tab)
  • Current differential protection of generator-transformer unit (87GT)
  • Current differential protection of generator (87G)
  • Current differential protection of main transformer (87T)
  • Current differential protection of step-down transformer (87T)
  • Current differential protection of excitation transformer or exciter (87E)

Generator protection (tab)
  • Phase segregated transverse differential protection (87STG)
  • Incomplete current differential protection (87IG)
  • High sensitive neutral point transverse differential protection (87NTG)
  • Generator inter-turn protection (59NIT)
  • Phase-to-phase impedance protection (21)
  • Voltage controlled overcurrent protection (50/51P)
  • Fundamental zero-sequence voltage stator ground fault protection (64S1)
  • Generator 3rd harmonic stator ground fault protection (64S2)
  • Generator stator ground fault protection with 20Hz voltage injection (64SInj)
  • Generator Ping-Pang type rotor ground fault protection (64R)
  • Rotor ground fault protection with low-frequency square-wave voltage injection (64RInj)
  • Stator overload protection (49S)
  • Excitation winding overload protection (49E)
  • Generator inadvertent energization protection (50/27)
  • Generator out-of-step protection (78)
  • Generator reverse power protection (32R)
  • Low forward power protection (32F)
  • Generator shaft overcurrent protection (51GS)
  • Overexcitation protection (24)
  • Loss-of-excitation protection (40G)
  • Overvoltage protection (59)
  • Undervoltage protection (27)
  • Underfrequency protection (81U)
  • Overfrequency protection (81O)
  • Negative-sequence overload protection (46G)
  • Generator startup and shutdown protection (StShut)
  • Breaker failure protection (50BF)
  • Voltage balance protection (60)

Main transformer protection
  • Transformer restricted earth fault protection (64REF)
  • Phase overcurrent protection of HV side (50/51P)
  • Phase-to-phase impedance protection of HV side (21)
  • Ground overcurrent protection of HV side (50/51G)
  • Gap zero-sequence overvoltage/overcurrent protection of HV side
  • Overexcitation protection (24)
  • Pole discrepancy protection of HV side (62PD)
  • Breaker flashover protection (50F)
  • Zero-sequence voltage alarm of LV side (59G)
  • Overload alarm
  • Initiating cooling

Step-down transformer protection
  • Overcurrent protection (50/51P)
  • Overcurrent protection includes two stages used as backup protection

Excitation transformer / Exciter protection
  • Voltage controlled overcurrent protection of HV side (50/51P)
  • Voltage controlled overcurrent protection of two branches of LV side (50/51P)
  • Residual overcurrent protection of two branches of LV side (50/51G)
  • Overload alarm
  • Initiating cooling

Miscellaneous functions
  • Mechanical protection (MR)
  • Fault detector (FR)
  • Voltage and current drift auto adjustment
  • VT circuit supervision (VTS)
  • CT circuit supervision (CTS)
  • Self diagnostic
  • GPS clock synchronization
  • Fault recorder
  • IEC61850 MMS & GOOSE for station bus
  • IEC60870-5-103 protocol
  • MODBUS protocol

Technical specifications
  • Applicable generator types: turbo-dynamo, gas-turbine, hydro, pumped storage, nuclear
  • Complete protection scheme for generator-transformer units including generator, main transformer, step-down transformer and exciter/excitation transformer
  • Supports conventional CT/VT and ECT/EVT
  • Provides interfaces for power plant automation
  • Duplicated protection configuration possible for medium to large generators using two PCS-985 units with different CT groups
  • Protection functions include differential protections (87GT/87G/87T/87E), multiple generator and transformer protections, rotor/stator ground fault schemes and frequency/voltage protections
  • Communications: IEC61850 MMS & GOOSE, IEC60870-5-103, MODBUS
  • Built-in fault recorder and GPS clock synchronization
  • Supervision and self-diagnostic features: VTS, CTS, voltage/current drift auto adjustment, self diagnostic
  • Mechanical and fault detection features: MR, FR
  • Cooling and overload management: overload alarm, initiating cooling