OverviewThe PCS-9611 is a feeder protection, control and monitoring relay designed for overhead lines, underground cables and transformer applications on solidly grounded, impedance grounded, Peterson coil grounded and ungrounded systems. It integrates a comprehensive function library, programmable logic, configurable I/O and frequency-tracking. Built on an advanced multiprocessor platform, the PCS-9611 fully complies with IEC 61850 station and process bus standards and supports IEC 61850-8-1 MMS, GOOSE and IEC 61850-9-2 Sampling Value.
Communication- Up to four 10Base-T/100Base-TX (RJ45) ports or two 100Base-FX ports; up to six 100Base-FX ports for IEC 61850-9-2 SV and GOOSE
- IEC 61850-8-1 MMS and GOOSE for non-time-critical messaging; IEC 60870-5-103 over TCP/IP or DNP3.0 support
- Two RS-485 rear ports with IEC 60870-5-103 and one additional RS-485 port for clock synchronization
- One RS-232 rear port for printer and one faceplate RJ45 port for testing and configuration
- Clock synchronization via pulse, IRIG-B and SNTP
Monitoring and Metering- Metering of current, voltage, active/reactive power, power factor, energy, frequency and harmonics
- Circuit breaker monitoring and tripping circuit supervision
- CT and VT failure supervision; line voltage failure detection
- Self-diagnostic functions, fault recorder, 1024 SOE entries and 64 oscillograms (COMTRADE)
Protection and Control- Six-stage overcurrent protection (67P, 50P/51P) and six-stage neutral/ground overcurrent (67G, 50/51G)
- Four-stage sensitive earth fault protection (67SG/51SG)
- Two-stage under/overvoltage (27/59), negative sequence overvoltage (47) and zero-sequence overvoltage (59G)
- Four-stage under-frequency, four-stage over-frequency and four-stage rate-of-change-of-frequency (81)
- Breaker failure protection (50BF), dead zone protection (50DZ), negative sequence overcurrent (46) and broken conductor detection (46BC)
- Thermal overload (49), undercurrent (37), switch-on-to-fault logic (SOTF), cold load pickup (CLP)
- 4-shot three-pole auto-reclosing with sync-check and dead line/bus check (79/25), interlocking logic for busbar protection, remote/local breaker trip and close, fault locator
- Automatic voltage and current drift adjustment; frequency tracking
Technical specifications- Model: PCS-9611
- Advanced multiprocessor platform; IEC 61850 station and process bus compliant
- Supports IEC 61850-8-1 MMS, GOOSE and IEC 61850-9-2 Sampling Value
- Ethernet ports: up to 4x10/100Base-TX (RJ45) or 2x100Base-FX; up to 6x100Base-FX for time-critical messages
- Serial ports: multiple RS-485 rear ports, RS-232 printer port
- Clock synchronization: pulse, IRIG-B, SNTP
- Protection functions: overcurrent, ground/neutral overcurrent, sensitive earth fault, under/overvoltage, negative/zero sequence protections, frequency protections, breaker failure, dead zone, broken conductor detection, thermal overload, undercurrent
- Control and monitoring: auto-reclosing, sync-check, dead line/bus check, SOTF, CLP, interlocking and breaker remote/local control; metering, 1024 SOE, 64 oscillograms (COMTRADE)