video corpo

Auxiliary electromechanical relay PCS-974
IEChigh-reliabilityhigh power

Auxiliary electromechanical relay - PCS-974 - NR Electric - IEC / high-reliability / high power
Auxiliary electromechanical relay - PCS-974 - NR Electric - IEC / high-reliability / high power
Add to favorites
Compare this product

Characteristics

Function
auxiliary
Other characteristics
IEC, high-reliability, high power

Description

Overview
PCS-974 is a mechanical auxiliary relay (IED) for transformer and generator non-electrical protection. It provides 16 high-power-pickup binary inputs designed for mechanical element monitoring, alarming and tripping, reducing susceptibility to EMI and improving operational reliability.

Protection and control
  • Up to 16 channels for mechanical protection (e.g., winding temperature, oil temperature, Buchholz, gas/pressure, oil level)
  • Self-diagnostic functions
  • Event recorder: 1024 change-of-binary-input events, 1024 supervision events, 1024 operation logs
  • Clock synchronization via IRIG-B, SNTP, PPS and PPM

Communication
  • Up to four 10Base-T/100Base-TX copper Ethernet ports supporting IEC 61850 (MMS, GOOSE), DNP3.0 or IEC 60870-5-103 over TCP/IP
  • Up to two 100Base-FX optical Ethernet ports (shared with copper ports) supporting IEC 61850, DNP3.0 or IEC 60870-5-103
  • Two RS-485 serial ports for IEC 60870-5-103
  • One RS-485 serial port dedicated to clock synchronization

User interface
  • Front HMI with large LCD and 9-button keypad
  • Front RJ-45 port for testing and configuration
  • Rear RS-232 or RS-485 port for printer
  • Language selection: English + one selected language
  • Configuration assistant: PCS-Explorer

Technical specifications & applications
  • Model: PCS-974
  • Product type: Transformer/generator auxiliary mechanical relay (IED)
  • Binary inputs: 16 high-power-pickup inputs for mechanical element monitoring, alarming and tripping
  • Supported protocols: IEC 61850-8-1 (MMS), IEC 61850 GOOSE, IEC 61850-9-2 Sampling Value (SV); DNP3.0; IEC 60870-5-103
  • Ethernet: up to 4 x 10/100Base-TX copper; up to 2 x 100Base-FX optical (shared)
  • Serial: two RS-485 for IEC 60870-5-103; one RS-485 for clock sync; one RS-232/RS-485 for printer
  • Event recorder capacity: 1024 change-of-binary-input events; 1024 supervision events; 1024 operation logs
  • Clock sync: IRIG-B, SNTP, PPS, PPM
  • HMI: large LCD with 9-button keypad
  • Front interface: RJ-45 port for testing and setting
  • Applications: mechanical protection for transformers and generators (winding/oil temperature, Buchholz, gas/pressure, oil level)
  • EMC mitigation: high-power-pickup design to reduce electromagnetic interference (EMI)
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.