Product OverviewThe Sag Simulator accepts two voltage inputs (normal and sag) and selectively outputs one of three states—Normal, Sag, or Open—to emulate voltage disturbance conditions. Operating sequences can be configured by phase, cycle/angle, and time. Integrated overcurrent protection interrupts the output instantly on load overcurrent to protect connected equipment. Used with an external variable autotransformer (Variac), transformer, or inverter-based source, the unit enables SEMI F47 voltage sag immunity testing.
Key Features- Input/Output Voltage: Three-phase, four-wire, 0–480 VAC
- Output Modes: Sag / Normal / Open, configurable per phase, timing and duration
- Switching Method: 4-step seamless transfer switching (no interruption)
- Trigger Interface: Digital Trigger Input (DIN) and Trigger Output (DOUT)
- Protection: Output overcurrent protection
- Cooling Method: Air-cooled
- Display: 7-inch LCD touchscreen (model-dependent: 8x20 character display on some units)
- Communication Interfaces: RS485 and CAN
- Remote Control: PC-based remote control software
- Supports SEMI F47 compliance testing when combined with external Variac, transformer or inverter-based supply
Product DescriptionThe Sag Simulator switches between two input sources to produce controlled voltage sag events and open-circuit conditions. Users program operating sequences using angle (phase) mode or time mode, set durations and repeat patterns, and monitor status and fault codes on the display. The device’s instantaneous overcurrent trip protects the DUT and prevents damage during tests. The simulator is suitable for laboratory and production-line immunity testing when paired with an appropriate external auxiliary power source.
Technical SpecificationsRated Input Voltage : Single-phase / Three-phase 200V–480V : Internal control transformer wiring configuration may be required
Variac (SL) Input Voltage : 0–510 VAC : For external variable autotransformer input
Input Frequency : 48–62 Hz :
Input/Output Current : Depends on rated capacity :
Sag Duration : 1–2000 cycles (≈16.7 ms–16.7 s) or 1–20000 ms (20 s) : Cycle Mode / Time Mode selectable
Cycle Duration : 1–2000 cycles or 1–20000 ms : Cycle Mode / Time Mode selectable
Display & Controls : 7-inch LCD touchscreen; model-dependent character display and push buttons :
Sync Pulse Output : Amplitude: 0–9 V; Polarity: Positive : Electrically isolated output
Operating Temperature : Ambient 15℃–45℃ :
Dimensions (W × D × H) : 550×400×200 mm (30 kVA); 716×500×330 mm (50 kVA); 716×500×500 mm (100 kVA); 1050×500×860 mm (200 kVA); 1000×600×1800 mm (400 kVA) :
Control Parameter (summary)Operating Modes: Angle Mode [Ang] (set start/end phase angles) and Time Mode [ms] (set start phase angle and duration). Output Voltage Modes: BYPASS (maintain normal), BYP>SAG, BYP>OPN, SAG (maintain sag), SAG>BYP, SAG>OPN, OPEN (maintain open-circuit), OPN>BYP, OPN>SAG. State indicators and fault codes include STOP, RDY, RUN, SAVE, GT_F (Gate Driver Fault), I_OV (positive-direction overcurrent), I_UN (negative-direction overcurrent), T_ER (over/under-temperature), V_NO (normal voltage input not detected). Parameters: Start Angle 0–359°, End Angle 0–359° (Angle Mode); Switching Duration 1–2000 cycles (Angle Mode) or 1–20000 ms (Time Mode); Repeat Interval (cycles or time); Repeat Count 0–1000 (0 = continuous); Angle Increment options (divide 360° into N parts or set custom increments); Operation indicator: CPU running shown by alternating symbol.