Product typeMicro-interruption compensator
SummaryOxygen Zero K is a micro-interruption compensator designed to maintain output voltage accuracy and protect critical loads from voltage disturbances. It uses IGBT technology combined with supercapacitors for voltage regulation and provides fast correction times (<5 ms) suitable for sensitive equipment.
Variants (summary table)Type | Efficiency | Rated power (kVA) | Input voltage variation [%] | Output voltage | Correction time
500K-1 | >99 | 500 | -100 | 400 | <5 ms
1000K-1 | >99 | 1000 | -100 | 400 | <5 ms
1500K-1 | >99 | 1500 | -100 | 400 | <5 ms
2000K-1 | >99 | 2000 | -100 | 400 | <5 ms
Key features- Frequency: 50Hz ±5% (60Hz ±5%)
- Voltage regulation: IGBT + Supercapacitors
- Selectable target voltage: 380-400-415V (440-460-480V)
- Output voltage accuracy: ±0.5%
- Admitted load variation: Up to 100%
- Admitted load imbalance [%]: 100
- Cooling: Forced ventilation
- Ambient temperature: 0/+40°C
- Storage temperature: 0/+60°C
- Max relative humidity: <95% (non condensing)
- Harmonic distortion: Harmonic tolerance according to IEC 61000-2-4 Class 2 (THDV < 8%)
- Colour: RAL 9005
Instrumentation- 10" touch panel, multilingual (remote access on request via dedicated software on the same Ethernet network)
InstallationIndoor
Communication systemMODBUS TCP/IP
Overvoltage protection- Class II output surge arrestors
Additional protections- Input automatic circuit breaker
- By-pass line with interlocked circuit breaker
- Output interlocked automatic circuit breaker
Technical specifications- Admitted load variation: Up to 100%
- Admitted load imbalance: 100%
- Cooling: Forced ventilation
- Ambient temperature: 0/+40°C
- Storage temperature: 0/+60°C
- Max relative humidity: <95% (non condensing)
- Harmonic distortion: THDV < 8% (IEC 61000-2-4 Class 2)
- Colour: RAL 9005
- Variants available: 500K-1, 1000K-1, 1500K-1, 2000K-1 (correction time <5 ms)