Input type (Universal input) : ※See the Input Range Code for the input range.
1)Thermocouple : K, J, T, S, R, E, B, N, W5Re/W26Re, U, L, PLII
2)RTD: Pt100 and JPt100 (3-wire system)
3)DC voltage/current: 0 to 10mV, 0 to 100mV, 0 to 20mA, 4 to 20mA
4)DC voltage: 0 to 1V, 0 to 5V, 1 to 5V, 0 to 10V, -5 to +5V,-10 to +10V
Sampling time: 0.01 sec.
Measurement accuracy : ±(0.1% of displayed value+1 digit) ※Depends on the input and the range.
Output 1 (OUT1) ※Control, Event, HBA (Heater Break Alarm), LBA (Control loop break alarm) or analog retransmission are assigned.
2)Voltage pulse output for SSR driving: 0/12V dc
3)Current output : 0 to 20mA, 4 to 20mA dc
4)Continuous voltage output: 0 to 5V, 1 to 5V, 0 to 10V dc
5)Transistor output: Allowable load current: 100 mA
Output 2 (OUT2) ※Control, Event, HBA (Heater Break Alarm), LBA (Control loop break alarm) or analog retransmission can be assigned
1)Relay contact output (b): 1a contact ※Highly durable relay
2)Voltage pulse output for SSR driving: 0/12V dc
3)Current output : 0 to 20mA, 4 to 20mA dc
4)Continuous voltage output: 0 to 5V, 1 to 5V, 0 to 10V dc
5)Transistor output: Allowable load current: 100 mA
Output 3 (OUT3) ※Universal output
1) Voltage pulse output for SSR driving: 0/14 dc
Digital output (DO: max.4 points)
Relay contact output: 1a contact
Event function (max.4 points)
Event inputs (Max.6 points)
Function of event inputs: RUN/STOP switching, AUTO/MAN switching, selecting Input 2, Interlock release, Peak/Bottom value release,