Electromechanical relay module FBB-2DI1DO-R.230
ACswitchingdigital

Electromechanical relay module - FBB-2DI1DO-R.230 - Romutec Steuer- u. Regelsysteme GmbH - AC / switching / digital
Electromechanical relay module - FBB-2DI1DO-R.230 - Romutec Steuer- u. Regelsysteme GmbH - AC / switching / digital
Electromechanical relay module - FBB-2DI1DO-R.230 - Romutec Steuer- u. Regelsysteme GmbH - AC / switching / digital - image - 2
Add to favorites
Compare this product

Characteristics

Type
switching, AC, electromechanical, digital
Applications
for actuators
Other characteristics
I/O, 2-channel
Protection level
isolated
Load current

16 A

Load voltage

230 V

Description

Product information
The FBB-2DI1DO-R.230 module provides two digital inputs and one relay output for decentralized switching tasks. It is designed to control motorized fire dampers with end-switch feedback (OPEN/CLOSED) and for general decentralized datapoints in building automation (remote I/Os).

Runtime measurement
For motorized fire dampers the module supports objects that record measured run times. Measurement occurs on every damper operation and captures total opening/closing time and dead time (time until leaving the original position is reported). Measured values are compared with maximum limits configured during commissioning.

Available variants / options
  • Supply voltage: selectable 24 V or 230 V. In R.230 variants the supply voltage is also switched to the relay output (L 230 V via the relay contact to the digital output).
  • Option "AMP": variants with AMP-style connector sockets for connecting preassembled cables from fire damper manufacturers.

Technical specifications
  • Product number: 00003221
  • Brand: romutec Steuer- und Regelsysteme GmbH
  • Model: FBB-2DI1DO-R.230
  • Function: 2 digital inputs, 1 relay output
  • Relay output: 230 V / 16 A (R.230 variants)
  • Supply voltage: selectable 24 V AC/DC or 230 V AC
  • Options: "AMP" connector variant
  • Bus interface: RS485, galvanically isolated
  • Protocol: BACnet MS/TP (RS485)
  • Supported baud rates: 9,600; 19,200; 38,400; 57,600; 76,800; 115,200
  • Operating temperature: 0...50°C
  • Storage/transport temperature: -10...70°C
  • Relative humidity: 10...90% non-condensing
  • Ingress protection: IP67 with cable glands; alternatives IP66 or IP54 depending on variant
  • Weight: 0.468 kg
  • Release date: 2026-04-28