• 3 phase RMS voltage protection relay
• Monitors: Over / Under Voltage, Over / Under Frequency, Phase asymmetry, Phase failure, Phase sequence & Neutral loss
• Accuracy: ± 1% of Voltage, ± 0.3Hz
• Measuring range : 160 to 520V depending on Network selection
• Supply Voltage : 85 to 270V AC/DC
• CE and RoHS Certified
Brief Specifications
Measuring Parameter : Under Voltage, Over Voltage, Under Frequency, Over Frequency, Phase Asymmetry, Phase Failure, Neutral Loss, Phase Sequence
Electrical Connection : 3Ø-3W, 3Ø-4W
Display : 3 Digits Liquid Crystal Display With Backlight
Trip Setting : Under / Over Voltage: 85 to 500V AC L-L (for 3Ø-3W),
50 to 288V AC L-N (for 3Ø-4W),
Under/Over Frequency: 45-65 Hz,
Voltage Asymmetry: 5.0-30.0%
Time Ranges : Trip Time Delay: 0-300sec, Power ON Delay: 0.5-300sec,
Recovery Time Delay: 0-300sec (In Auto Reset mode),
Response Time: <120ms
Accuracy : Trip Voltage: ±1% ±2 digits,
Frequency: ±0.5% ±1 digit,
Time Setting Accuracy: ±5% of setting ±120ms
Output Contact : 2 x 1 C/O (SPDT)
Output Rating : NC: 3A@250V AC, NO: 5A@250V AC (Res)
Operating Voltage : 50 to 288V AC (L-N),
85 to 500V AC (L-L)
Size : 35mm
Mounting Type : DIN Rail Mount
Certification : CE