Fire alarm control panel ECP1000
gasnetworked

Fire alarm control panel - ECP1000 - Shenzhen HTI Sanjiang Electronics Co., Ltd. - gas / networked
Fire alarm control panel - ECP1000 - Shenzhen HTI Sanjiang Electronics Co., Ltd. - gas / networked
Add to favorites
Compare this product

Characteristics

Alarm type
fire, gas
Other characteristics
networked

Description

Product features
New-generation high-speed microprocessor for significantly faster data processing and greatly increased storage compared with traditional technologies.
4.3-inch color LCD display, resolution 480 × 272.
USB support for importing/exporting system configuration and history files to simplify maintenance.
Support for multi-panel networking via CAN or Ethernet.
Event history: 10,000 records each for fire alarms, faults and operations.
Hierarchical multi-level user management with configurable operation permissions.
Field-upgradeable firmware to maintain system reliability.
Optional modules available: host networking module, intelligent Class A module.

Product Info
The EPC1000 is an integrated fire alarm and gas extinguishing control panel designed in accordance with EN 54-2, EN 54-4 and EN 12094-1. It provides fire detection and, on fire confirmation, can automatically or manually release extinguishing gas to suppress the fire in the protected environment.

Technical Parameters
Mains supply: 110V/230V AC (-15%, +10%), 50Hz/60Hz
Mains fuse: T3AL250V
Power supply rating: 10A, 28V ±1V
Battery type (recommended): 7Ah VRLA, NP7-12 (Yuasa)
Battery charge voltage: 27.6V DC nominal (temperature compensated)
Charging current: 1A max
Battery fuse: 8A, φ5×20mm glass
Maximum internal resistance of battery: 1Ω
Maximum current draw from batteries (when mains disconnected): 8A
Imax.a: 3.2A
Imax.b: 3.8A
Imin.: 0.1A

Technical specifications
  • Model: EPC1000
  • Standards: Designed in accordance with EN 54-2, EN 54-4 and EN 12094-1
  • Processor: New-generation high-speed microprocessor (≈100× processing speed, ≈1000× storage vs traditional)
  • Display: 4.3-inch color LCD, 480 × 272 resolution
  • Data transfer & maintenance: USB support for importing/exporting configuration and history files
  • Networking: Supports multi-panel networking via CAN or Ethernet
  • Event history: 10,000 records each for fire alarm, fault and operation
  • User management: Hierarchical multi-level user management with configurable permissions
  • Field upgradeable: On-site system upgrade capability
  • Optional modules: Host networking module, intelligent Class A module
  • Power — Mains supply: 110V/230V AC (-15%, +10%), 50/60Hz
  • Mains fuse: T3AL250V
  • Power supply rating: 10A, 28V ±1V
  • Battery: 7Ah VRLA, recommended NP7-12 (Yuasa)
  • Battery charge voltage: 27.6V DC nominal (temperature compensated)
  • Charging current: 1A max
  • Battery fuse: 8A, φ5×20mm glass
  • Maximum internal resistance of battery: 1Ω
  • Maximum current draw from batteries (mains disconnected): 8A
  • Imax.a: 3.2A
  • Imax.b: 3.8A
  • Imin.: 0.1A

Catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.