Relative humidity and temperature probe DB4385
duct-mountresistanceRS-485

Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 2
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 3
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 4
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 5
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 6
Relative humidity and temperature probe - DB4385 - DABECO Co.,Ltd - duct-mount / resistance / RS-485 - image - 7
Add to favorites
Compare this product

Characteristics

Type
relative
Mounting
duct-mount
Technology
resistance
Output
RS-485, Modbus RTU
Supply voltage
12VDC, 15VDC, 24VDC
Electrical connection
terminal block
Protection level
waterproof
Other characteristics
precision, programmable
Applications
for industrial applications, for building automation, for HVAC
Measuring range (%)

Min.: 0 %

Max.: 100 %

Precision

3 %

Measuring range (temperature)

Min.: -40 °C
(-40 °F)

Max.: 120 °C
(248 °F)

Accuracy (temperature)

0.4 °C
(32.72 °F)

Working temperature

Min.: -40 °C
(-40 °F)

Max.: 120 °C
(248 °F)

Description

RS485 Interface Duct Humidity and Temperature Sensor for HVAC DB4385 sensor is designed to measure the temperature and relative humidity of interior air in spaces by a common internal sensor, whose signal is processed by a microprocessor and converted into a MODBUS RTU output signal. It is widely used in measurement scenarios such as industrial sites, telecommunication base stations, offices, supermarkets, production workshops, warehouses, and construction sites. Specification Measurement range - Humidity:0%RH~100%RH; Temperature:-40~120℃(measurement range supports customization) Accuracy@20%RH~80%RH @25℃ - Humidity:±3%RH; Temperature:±0.4℃ Interface - RS485, Modbus RTU Response time - 1.6s Programmable address - 1~255 Baud rate - 1200~115200 Supply voltage - 12~24VDC Transmitter operating temperature - -20℃~80℃ Power consumption - <4W Material - Transmitter:cast aluminum; Probe:304 stainless steel; Probe:copper sintering