• Max. 2 A current output
• Color: Orange/ Grey/ Yellow/ Blue/ Red
• Without maintenance timer
• Including the "daily ventilation" function
• One SHEV group (RG) and one ventilation group (LG)
• PC service port interface for extended configuration options
• Built-in power supply 230 V AC/24 V DC, emergency batteries and charging unit for 72 hours of operational readiness in the event of a power failure
• Optionally available as a flush-mounted version
• TÜV type-tested
• Tested in accordance with EN 12101-10:2005/AC:2007
Material
• Plastic housing for surface mounting
Connection options
• 24 V DC drives with own load or limit switching with a total current consumption of max. 2 A
• 10 SHEV control panels RBH/3A...
• 10 automatic detectors in 2-wire technology
• 10 external ventilation open/stop/close buttons (with or without open display)
• 24 V DC siren or flashing light, max. 100 mA
• One connection each for potential-free signaling: SHE triggered (NO contact) and fault (NC contact); 24 V / max. 0.5 A