GeneralThe (H)RW12 series outdoor high-voltage drop-out fuse provides short-circuit and overload protection and enables breaking/closing of load currents for distribution transformers and branch lines. The device comprises an insulating support and a fuse tube; static contacts are mounted on the support and moving contacts on the fuse tube. The fuse tube includes an inner arc‑extinguishing tube and an outer epoxy fiberglass tube.
Service conditions- Altitude: ≤ 2000 m.
- Ambient temperature: Max +40°C, Min -30°C.
- Installation site: free from explosion hazards, severe vibration and aggressive corrosive conditions.
Technical parametersType | Rated voltage (kV) | Rated current (A) | Breaking current (A) | Impulse voltage (BIL) | Power-frequency withstand voltage (kV) | Creepage distance (mm) | Weight (KG) | Dimension (cm)
(H)RW12-12 | 12 | 100 | 1000 | 110 | 42 | 31.5 | 7.3 | 38.5 x 34.5 x 11
(H)RW12-12 | 12 | 200 | 1200 | 110 | 42 | 31.5 | 7.3 | 38.5 x 34.5 x 11
(H)RW12-15 | 15 | 100 | 1000 | 110 | 42 | 31.5 | 7.3 | 38.5 x 34.5 x 11
(H)RW12-15 | 15 | 200 | 1200 | 110 | 42 | 31.5 | 7.3 | 38.5 x 34.5 x 11
Electrical / Mechanical dimensions and parameters (detailed)Rated voltage (kV) | BIL (kV) | A (mm) | B (mm) | C (mm) | D (mm) | E (mm) | F R (mm) | Creepage distance (mm) | Weight (KG)
12(15) | 125 | 331.4 | 169.3 | 202.4 | 462.8 | 129.4 | 412.8 | 325.1 | 6.58
24(27) | 125 | 341.4 | 179.3 | 202.4 | 462.8 | 134.9 | 412.8 | 325.1 | 6.58
24(27) | 150 | 341.4 | 179.3 | 202.4 | 462.8 | 134.9 | 412.8 | 457.2 | 9.08
27(33) | 200 | 435.1 | 187.5 | 261.1 | 548.4 | 165.1 | 522.2 | 665.5 | 10.1
27(36) | 200 | 435.1 | 187.5 | 261.1 | 548.4 | 165.4 | 522.2 | 769.6 | 10.1
Outline structure and installation dimensions- Upper terminal block (tin‑plated copper castings or silver‑plated stamped parts).
- Upper cover in 304 stainless steel with integrated terminals.
- Upper contact plate (zinc‑plated integrated terminal block) to improve conductivity.
- Upper moving contact plated with 3 µm silver and fitted with a 304 stainless spring for high contact pressure.
- Tripping hook designed to guide the fuse tube into the closed position.
- Fuse tube: UV‑resistant, moisture‑proof; inner arc‑extinguishing tube and outer epoxy fiberglass tube.
- Trunnion plated with 3 µm silver to ensure precision and prevent lateral movement during closure.
- Lower moving contact with 3 µm silver‑plated shunt plate providing a current path independent of the hinge pin.
- Rapid separation at the ends and quick ejection of the cable strand.
- High‑strength insulator with self‑cleaning properties.
- Base terminal (zinc‑plated integrated lower terminal block).
Materials and treatmentsIron accessories are hot‑dip galvanized (>80 µm). Stainless steel components use grade 304. Contact surfaces are silver‑plated (3 µm). Precision‑cast brass or aluminum bronze are available as material options for specific parts.
Characteristics / technical specifications- Product type: outdoor high‑voltage drop‑out fuse for protection of distribution transformers and branch lines.
- Primary functions: short‑circuit and overload protection; breaking and closing of load currents.
- Rated voltages: 12 kV, 15 kV (additional 24/27 kV variants listed in detailed table).
- Rated currents: 100 A and 200 A.
- Breaking currents: typically 1000 A (100 A models) and 1200 A (200 A models).
- Impulse voltage (BIL): up to 200 kV depending on variant.
- Operating altitude ≤ 2000 m; ambient temperature range -30°C to +40°C.
- Typical dimensions and weight vary by model (e.g. 38.5 x 34.5 x 11 cm; 6.58–10.1 kg).