Room pendulum sensor for sectional measurement of relative humidity and temperature in large and high spaces (e.g. exhibition halls, churches and similar applications). Alternatively, the output can also be set to measure absolute humidity, enthalpy or dew point rather than relative humidity. The design ensures optimal installation and precise measurements. The accuracy of the humidity sensor is 2%.
• Application/type : Pendulum sensor, Room sensor
• Purpose : Measure values
• Measured values : temperature, relative humidity, absolute humidity, enthalpy, dew point
• Interface : Active, 0..5 V, 0..10 V, 4..20 mA
• Configuration : jumper
• Output voltage : 2x 0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 10 kΩ
• Output current : 2x 4..20 mA, max. load 500 Ω
• Output signal temperature : -20..+80 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C, adjustable at the transducer
• Operating range humidity : max. 85% rH short term condensation
• Accuracy temperature : ±0,3 K (typ. at 21 °C), within default measuring range, potentiometer for offset adjustment, offset setting via app or uConfig
• Measuring range humidity : 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, adjustable at the transducer
• Accuracy humidity : ±2% between 10..90% rH (typ. at 21 °C), potentiometer for offset adjustment
• Power supply : 15..24 V = (±10%) SELV, 24 V ~ (±10%) SELV
• Power consumption : typ. 0,4 W (24 V =), typ. 1 W (24 V =), 0,8 VA (24 V ~)