Product overviewOn-line double-conversion UPS providing fully regulated pure-sine output for sensitive IT, healthcare, education and other mission-critical applications. Convertible 2U rack/tower form factor with optional external battery modules for extended runtime. ENERGY STAR 2.0 certified for energy-efficient operation.
Key features- On-line (double-conversion) topology isolates connected equipment and supplies continuous pure sine-wave output.
- Rated 1000 VA / 900 W (208V default); configurable for 220/230/240 V to deliver up to 1000 W.
- Zero transfer time between online and battery modes to ensure uninterrupted operation.
- Front-access, hot-swappable VRLA battery cartridge; runtime expandable by up to 4 external battery modules (EBMs, e.g., BP48RT).
- Optional LX-platform network management card (WEBCARDLXE) for remote monitoring, SNMP and managed shutdowns.
- Rotatable front-panel LCD for status, event logs and configuration.
- Eight IEC C13 outlets arranged in two switchable load banks for selective load shedding to preserve runtime for critical loads.
- EMI/RFI filtering and surge suppression (296 J); USB and RS-232 (DB9) communications plus dry-contact relay for integration.
- Includes 4-post rack-mount hardware and tower support stands; 2U rack height.
- ENERGY STAR 2.0 certified; high-efficiency economy mode available to reduce operating costs.
Package includes- SmartOnline 1000VA 900W 208/230V Double-Conversion UPS (2U)
- USB communication cable
- DB9 (RS-232) cable
- Two IEC 10A 6 ft output cables
- Rack-mounting hardware (4-post)
- Tower support stands
- Safety instructions and quick start guide
Notes- Optional external battery module: BP48RT (48V EBM) compatible with 2025 design update; supports up to 4 EBMs for extended runtime.
- Optional network management card: WEBCARDLXE (remote monitoring and control).
Technical specifications- UPS type: On-line double-conversion; UPC: 037332185648
- Input: Single-phase; nominal voltages 200/208/220/230/240 V AC; C14 inlet; input current max 6 A; frequency range 40–70 Hz before transfer to battery.
- Output: 1000 VA / 900 W (208V default); 220/230/240 V = 1000 VA / 1000 W; power factor 0.9; crest factor 3:1; pure sine wave in line and battery modes; frequency tolerance ±0.5% (battery).
- Output receptacles: 8 × IEC C13; two switchable load banks (selectable outlets per bank).
- Battery: Internal VRLA cartridge; DC system voltage 48 V; front battery access; recharge ≈ 3 hours to 90%.
- Runtime: Full load (900 W) ≈ 7.3 minutes; half load (450 W) ≈ 17.9 minutes; expandable with up to 4 EBMs (BP48RT).
- Form factor & physical: 2U rackmount / tower convertible; dimensions (H×W×D) 3.410 × 17.330 × 17.720 in; unit weight 36.38 lb; housing metal.
- Environment: Operating 0°–40°C; storage w/battery 0°–40°C, w/o battery −25°–55°C; humidity 0–96% non-condensing; audible noise ≈ 40 dBA.
- Communications: USB and RS-232 (DB9) included; dry-contact relay; slot for optional WEBCARDLXE; supports PowerAlert and watchdog restart.
- Safety & compliance: UL 1778, cTUVus, CAN/CSA-C22.2 No. 107.3, NOM, CE, RoHS; ENERGY STAR qualified.
- Surge/noise suppression: 296 J, instantaneous response.
- Warranty: 2-year limited warranty; Ultimate Lifetime Insurance $250,000 (where applicable).