Product overviewThe LINETRAXX® PEM353 is a digital universal measuring device for recording and displaying electrical quantities of supply networks and providing them via a communication interface. It measures voltages, currents, power and energy and evaluates voltage quality (THD and individual harmonics up to the 31st order). Suitable for 2-, 3- and 4‑wire systems and TN, TT and IT topologies. Standard front-panel dimensions: 96 x 96 mm.
Main features / functions- Comprehensive measured quantities: voltages, currents, power, energy, harmonics, unbalance, angles, THD/TDD, k‑factor, crest factor
- Power Quality Monitoring and limit value monitoring (setpoints) with alarm forwarding
- Energy and power measurement with storage, Time of Use (up to 8 tariffs)
- Configurable start page showing 4 measured quantities
- N conductor measurement and monitoring (PEM353‑N)
Measurement details- Phase voltages UL1, UL2, UL3 and sum (V)
- Line‑to‑line voltages UL1L2, UL2L3, UL3L1 and sum (V)
- Phase currents I1, I2, I3 and sum (A); neutral current In (calculated) and I4 measured on PEM353‑N
- Residual current Ir (calculated, PEM353‑N)
- Frequency f (Hz)
- Per‑phase and total power: P (kW), Q (kvar), S (kVA)
- Displacement factor cos(φ), power factor λ, phase angles (°)
- Voltage/current unbalance (%)
- Harmonics and distortion: THD/TOHD/TEHD for U and I; individual harmonics to 31st order; TDD for I
- k‑factor and crest factor for currents
Energy meters- Active energy accuracy class acc. IEC 62053‑22: 0.5 S
- LED pulse output for active or reactive energy
- 2 pulse outputs (PEM353‑P)
- Total and per‑phase energy: import/export, net and total for active/reactive and apparent energy
- Up to 4 additional pulse counters (e.g. gas, water)
Times of Use / Tariffs- Up to 8 tariffs with tariff switching via digital inputs or schedule (2 schedules)
- Energy metering per tariff and peak demand per tariff
Logs and recording- Energy meter log — 12 monthly values (total and per tariff)
- Load data: configurable sliding averages, demand forecasts, peak demand log with timestamp
- Max./min. log for 45 quantities with timestamp
- Event log (SOE) — 100 entries with 1 ms resolution
- PEM353‑N: daily (60 days) and monthly (36 months) logs; up to 5 data recorders with up to 16 channels each
Limit value monitoring / Alarms- 9 parameterisable monitoring points (setpoints)
- Choose from 25 measured quantities for setpoints
- Alerting via display and/or digital outputs; adjustable hysteresis
Operation & usability- Large backlit graphic display; configurable standard page with 4 values
- Display password protection and operating hours counter
- Connection fault detection (frequency, voltage/current failure, CT polarity, rotating field)
Communication and protocols- Galvanically isolated RS‑485 interface (1,200–38,400 bit/s)
- LED for communication activity
- Supported protocols: Modbus RTU, BACnet MS/TP, DNP
Applications- Front‑panel instrument for electrical quantity indication and replacement of analogue indicators
- Power quality monitoring and energy data collection for energy management systems
- Limit value monitoring with alarm forwarding; N conductor monitoring where required
Variants- PEM353 | 3(N)AC 230/400 V | I1/I2/I3 = 5 A | I4 = - | 2 relay outputs | Art. No. B93100355
- PEM353‑P | 3(N)AC 230/400 V | I1/I2/I3 = 5 A | I4 = - | 2 solid‑state pulse outputs | Art. No. B93100354
- PEM353‑N | 3(N)AC 230/400 V | I1/I2/I3 = 5 A | I4 = 5 A | 2 relay outputs | Art. No. B93100353
Optional accessories (selection)- Window‑type current transformers (CTB31, CTB41) — various primary currents (60 A … 1000 A), secondary 5 A or 1 A, multiple accuracy classes
- Split‑core current transformers (KBR18, KBR32) — various ratios and accuracies
Technical specifications- Model name: LINETRAXX® PEM353; dimensions 96 x 96 mm (front panel)
- Supported topologies: 2/3/4‑wire, TN/TT/IT; nominal system voltage 3(N)AC 230/400 V
- Standard current inputs: 5 A (I1–I3); additional I4 = 5 A on PEM353‑N
- Energy accuracy: IEC 62053‑22 class 0.5 S; logging and recorder functions as above
- Interfaces: galvanically isolated RS‑485; Modbus RTU, BACnet MS/TP, DNP