OverviewThe ISOSCAN® EDS151 is an insulation fault locator for automatic feeder-by-feeder fault finding in unearthed (IT) power systems when used with ISOMETER® isoMED427P. It detects locating current pulses via six integrated measuring current transformers and evaluates faults for rapid alarm and display.
Key features- Automatic insulation fault location during operation
- Intended application: control and monitoring circuits
- 6 measuring channels with integrated current transformers
- RS-485 bus connectivity (BMS protocol) for scalable monitoring
- Cyclical self-test and bus activity indication
Features (detail)- Suitable for AC, AC/DC and DC IT systems
- Response sensitivity: 0.5 mA
- Maximum response time (alarm + indication): ≤ 8 s in AC systems (IEC 61557-9)
- Up to 88 EDS151 devices per RS-485 bus → up to 528 circuits monitored
- BMS address range: 3…90
- RS-485 interface with BMS protocol
Applications- Insulation fault location in medical, industrial and maritime IT systems
- DC main circuits in plants, power stations and ships
- Monitoring of control and signalling circuits
ISOSCAN® EDS151 Variant(s)Type | Supply voltage* | Art. No.
EDS151 | AC 17…24 V, 50…60 Hz / DC 14…28 V | B91080101
Optional Accessories (selection)Type | Supply voltage | Output voltage | Art. No. | Note
AN410 | AC 90…264 V, 47…63 Hz / DC 120…370 V* | DC 24 V, 420 mA | B924209 | Supplies up to 6 EDS151
AN450 | AC 230 V, 50…60 Hz | AC 20 V, 500 mA | B924201 | Supplies up to 3 EDS151
Downloads (available documents)- Datasheet: EDS151 (EN)
- Manual: EDS151 (EN)
- CE Declaration of Conformity: EDS151
- Product Change Notification: EDS151 - Change of software (EN)
- Flyer: Healthcare EDS
- Flyer: Industrial EDS
NotesThe locating pulses generated by ISOMETER® isoMED427P are detected by the integrated CTs and evaluated by the EDS151. Integrated CTs allow all active conductors of an outgoing line to be routed through a single device. Bus coupling enables scalable monitoring of multiple circuits.
Technical specifications- Model name: ISOSCAN® EDS151
- Measuring channels: 6 per device
- Integrated measuring current transformers: 6
- Response sensitivity: 0.5 mA
- Maximum response time: ≤ 8 s (IEC 61557-9)
- Bus/interface: RS-485 with BMS protocol
- Max devices on BMS bus: 88 (up to 528 circuits)
- BMS address range: 3…90
- Supply voltage (EDS151): AC 17…24 V, 50…60 Hz or DC 14…28 V
- Accessory power supplies: AN410 (DC 24 V, 420 mA) supplies up to 6 EDS151; AN450 (AC 20 V, 500 mA) supplies up to 3 EDS151
- Self-test: cyclical self-test function
- Art. No. (EDS151): B91080101