DIN rail power supply ALE2405
AC/DCsingle-outputregulated

DIN rail power supply - ALE2405 - ELC construction électronique - AC/DC / single-output / regulated
DIN rail power supply - ALE2405 - ELC construction électronique - AC/DC / single-output / regulated
Add to favorites
Compare this product

Characteristics

Mounting / format
DIN rail
Type
AC/DC
Output
single-output, regulated, stabilized, adjustable
Technology
switching, PWM
Network
single-phase
Protection
with short-circuit protection, with overcurrent protection, with surge protection
Certifications
CE, RoHS
Connection
with screw terminal block
Applications
for marine applications, for industrial applications, for telecommunications equipment, emergency battery, electronic equipment, for automation, for electrical networks, workstation, for telecom applications, for railway applications, for access control, for distribution panels, for control boxes
Secondary function
battery charger
Other characteristics
with power factor correction, low-noise level, robust, safety, RoHS compliant, isolated, low-voltage, compact
Input voltage

230 V

Min.: 220 V

Max.: 240 V

Output voltage

24 V

Min.: 20 V

Max.: 29 V

Current

5 A

Min.: 0 A

Max.: 5 A

Power

120 W

Description

• Floating outputs on plug-in terminal block for 2.5 mm² (AWG 12) wire • Output voltage : adjustable from 20 to 29 V. • Regulation : < 20 mV for a load variation from 0 to 100%. < 1 mV for a line variation from -10 to +10%. • Ripple : < 3 mV rms including: < 5 mV peak to peak of the signal at 100 kHz < 5 mV peak to peak of the signal at 100 Hz < 15 mV peak to peak of switching spikes • Hold-up time : 25 ms at half load and 12 ms at full load (190 V line input). • Indicator : green power-on LED indicator. “status, output fault” red LED. Current • Max I : 5,5 A in short circuit condition. 5 A from 20 to 29 V Power • Max output power : 145 W. Protection • Against short circuit protection, by current limit. • Against overcurrent on primary circuit, by fuse. • Against overload on outputs, by voltage limit to 33 V. Other specifications • Safety : Complies with EN 61010-1, EN61010-2-201 and EN 62368-1. • EMC : Complies with EN 61000-6-2 and EN 61000-6-4. • Insulation Class : I. • Overvoltage Category : II. • Pollution Degree : 2. • Installation altitude : < 2000 m. • Protection level : IP 30. • Operating temperature : from -10 to +60 °C ; derating : 2.5%/K from +50 °C • Input voltage : 220-240 VAC (190 to 264 Volts), 50-60 Hz. • Mains input : 3-pole plug-in terminal block for 2.5 mm² (AWG 12) wire. • DC ouput : 2-pole plug-in terminal block for 2.5 mm² (AWG 12) wire. • Power consumption : 170 W max. • Power factor : 0,99 (built with PFC). • Dielectric strength : 3000 VAC 1800 VAC from input to chassis. • Presentation : galvanized steel case and front panel with epoxy finish. • Mounting : Integral symmetrical DIN rail clips
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.