Installing parameters using Prokey
Password protection for programming section
Adjustable internal buzzer according to
sensor defect status
4 Digits Display
NTC Input or PTC Input or
J type thermocouple Input or Ktype
thermocouple Input or
2-Wire PT-100 Input ori 2-Wire PT-1000 Input
(Must be determined in order.)
Adjustable temperature offset
ON/OFF temperature control
Selectable heating or cooling function
Remote acces, data collecting and controlling with Modbus RTU (Optional)
Dimensions - 76mm x 34,5mm x 71mm
Installation - Fixed Installation
Storage Temperature - -30°C to +80°C
Storage / Operating Humidity - 90 % max. (None condensing)
Electrical Features
Supply Voltage and Power - 24Vdc/ac ( ±%15) 50/60Hz - 2.5VA
24 V ac (±%15) 50/60 Hz. 2.5 VA
115 Vac (±%15) 50/60 Hz. 2.5 VA
230 Vac (±%15) 50/60 Hz. 2.5 VA
100-240Vac 50/60Hz 2.5 VA
10-30Vdc 2.5W
Sensor Inputs - NTC, PTC, TC, RTD
NTC (10k @.25 °C)
PTC(1000 @.25 °C)
J, K (IEC584.1)(ITS90)
PT-100, PT-1000 (IEC751)(ITS90)
Optional Sensor Inputs -
Scale - Fe-CuNi 0°C...800°C
NiCr-Ni 0°C...999°C
PT 100 -50°C...400°C / -19.9°C...99.9°C
NTC -50°C...100°C
PTC -50°C...150°C
Accuracy - ± % 1 of full scale
Output
Relay Output - 16(8)A@250 Vac at resistive load
SSR Output - Maximum 20mA, Maximum 17Vdc
Analogue Output -
Optional Outputs -
Control
Control Form - On/Off
Reading Frequency - 3 readings per second
Communication Protocols - RS-485, Prokey Programming Module
Approvals - EAC, CE