The CRV-13 relay switches when a minimum or maximum voltage threshold is reached, thus protecting electrical devices from inappropriate voltage risks:
- **Electrical:** For single-phase network.
- **Relay:** 1 single-pole changeover contact 16A/250V.
- **Programming:** Maximum threshold (Umax) adjustable from 160 to 276V.
Minimum threshold adjustable from 30 to 75% of Umax.
Delay time adjustable from 0.5 to 10 seconds.
- **Physical:** Relay housing width 18 mm, DIN rail mountable.
Adjustment via front panel levers.
- **The relay switches if:** The voltage reaches the minimum or maximum threshold and the delay time has elapsed.
- **Applications:** Protects electrical devices from inappropriate voltages; and/or triggers an alarm in case of abnormal voltage value.
- **Conformities:** CE, RoHs, REACH.
- **Applicable Standards:** EN 60255-1, EN 60255-26, EN 60255-27.
**Features / Technical Specifications:**
- For single-phase network
- 1 single-pole changeover contact 16A/250V
- Maximum threshold (Umax) adjustable from 160 to 276V
- Minimum threshold adjustable from 30 to 75% of Umax
- Delay time adjustable from 0.5 to 10 seconds
- Relay housing width 18 mm, DIN rail mountable
- Adjustment via front panel levers
- Conformities: CE, RoHs, REACH
- Standards: EN 60255-1, EN 60255-26, EN 60255-27