OverviewThe PCS-986 disturbance and fault recorder is engineered for monitoring and recording electrical parameters and operational events of generator-transformer units and power plant protection & control devices. Its modular unit architecture enables flexible hardware and software assembly and future upgrades.
Communications- 1 RJ45 Ethernet port supporting IEC60870-5-103 and IEC61850
- 1 RS-485 serial port for GPS time synchronization
- 1 RS-232 serial port for device testing and configuration
- 1 dedicated Ethernet interface for FTP continuous recording and real-time waveform display
Auxiliary Function- Self-diagnostic tests
- DC power loss alarm
- Hardware circuit online detection
- IRIG-B time synchronization support
Recording Functions- Triggers based on AC voltage
- Phase voltage sudden change
- Positive-sequence voltage sudden change
- Zero-sequence voltage sudden change
- Triggers based on AC current
- Phase current sudden change
- Positive-sequence current sudden change
- Zero-sequence current sudden change
- Triggers for voltage/current out-of-limit
- Triggers for positive/negative sequence component limits
- Triggers for DC sudden change or DC component limits
- Frequency out-of-limit and sudden change detection
- Third harmonic out-of-limit detection
- Over-excitation and reverse power detection
- Low-frequency overcurrent / zero-sequence voltage for startup/shutdown
- Differential current monitoring for main, step-down, generator or excitation transformers
- Triggers from binary inputs, system oscillation, manual and remote initiation
- Continuous 24-hour recording capability
Technical specifications- Model series: PCS-986
- Designed for generator-transformer units and power plant protection & control devices
- Modular unit architecture for hardware and software upgrades
- Supported protocols: IEC60870-5-103, IEC61850
- Ethernet: RJ45 port and separate Ethernet interface with FTP support for continuous storage and real-time waveform
- Serial ports: RS-485 (GPS sync), RS-232 (test/config)
- Time sync: GPS via RS-485, IRIG-B support
- Alarms/diagnostics: self-diagnostic, DC power loss alarm, hardware online detection
- Recording triggers: voltage/current sudden changes, sequence component changes, DC changes, frequency/harmonic limits, over-excitation, reverse power, differential current, binary inputs, system oscillation
- Recording modes: manual, remote, automatic triggers, continuous 24h recording
- FTP storage support for continuous recordings