IEC/EN Category: C1/C2/C3
Mode of Protection: Longitudinal, Transverse
Location of Use: DC Power Systems
Coarse Protection: MOV
Voltages: 12, 24, 48 V DC
Surge Discharge Ratings: In: 10 kA, Imax: 20 kA
Serial Inductivity: 10 – 14 μH
Series Load Current: 4 A
Enclosure: DIN 43880 2/3 TE, DIN Rail Mount
Terminals: Stranded to 4 mm2
Housing: Modular Design
Compliance: IEC/EN 61643-21
The RayDat PSC-2 Series has been developed to protect power supplies. Coarse protection is provided by varistors, while fine protection is provided using a high-speed silicon stage. Internal thermal disconnectors are used to reduce the hazards of thermal runaway during fault conditions, or if mains incursion onto the low voltage data circuit occurs. If the module is unplugged out of the base, the connection lines remain enabled.