PRODUCT OVERVIEWThe electromechanical hygrostat MFR-012 is designed to control enclosure heaters so the dew point is raised when a critical relative humidity (65%) is exceeded, preventing condensation and corrosion in electrical cabinets.
KEY FEATURES- Adjustable relative humidity
- Change-over contact
- High switching capacity
- Easily accessible terminals
- 35 mm DIN-rail mounting
TECHNICAL DATASwitch difference: 4% RH (+3% tolerance)
Permissible air velocity: 15 m/sec
Contact type: change-over contact
Contact resistance: <10 mΩ
Service life: >100,000 cycles
Min. switching capacity: 20 V AC/DC, 100 mA
Max. switching capacity: 250 VAC, 5(1) A; DC 20 W
EMC: acc. to EN 55014-1-2, EN 61000-3-2, EN 1000-3-3
Connection: 3-pole terminal, clamping torque 0.5 Nm max.; rigid wire 2.5 mm²; stranded wire (with ferrule) 1.5 mm²
Mounting: clip for 35 mm DIN rail EN 60715 or for exit filter EF 118 Series
Housing: plastic according to UL94 V-0, light grey
Dimensions: 67 x 50 x 38 mm
Weight: Approx. 60 g
Installation position: variable
Operating / Storage temperature: -20 to +80 °C / -45 to +80 °C
Protection type: IP20
ARTICLE / SETTING RANGEArt.No.: 01220.0-00 — Setting range: 35 to 95% RH
CHARACTERISTICS / TECHNICAL SPECIFICATIONS- Model: MFR-012
- Function: electromechanical hygrostat for controlling enclosure heaters to avoid condensation
- Adjustment range: 35–95% RH (Art.No. 01220.0-00)
- Switching sensitivity: 4% RH (± tolerance)
- Max. permissible air speed: 15 m/s
- Contact: change-over contact; contact resistance <10 mΩ
- Service life: >100,000 cycles
- Electrical ratings: min. 20 V AC/DC, 100 mA; max. 250 VAC, 5(1) A; DC 20 W
- Connection: 3-pole terminal, clamping torque 0.5 Nm max.; rigid up to 2.5 mm², stranded up to 1.5 mm² (with ferrule)
- Mounting: 35 mm DIN rail clip (EN 60715)
- Housing material: UL94 V-0 plastic, light grey
- Protection class: IP20
- Operating temperature range: -20 to +80 °C; storage down to -45 °C
- Dimensions (W x H x D): 67 x 50 x 38 mm
- Weight: approx. 60 g