PRODUCT OVERVIEWThe compact high-performance fan heater prevents condensation and maintains an even interior air temperature in enclosures housing electrical or electronic components. The plastic casing provides double insulation and touch protection. The unit is offered with an integrated thermostat or a factory-set hygrostat for temperature or humidity control. The CR 030 is designed as a stationary bottom-mounted unit; the CR-130 is recommended for wall fixing.
KEY FEATURES- Compact design for enclosure integration
- Double insulated (Class II)
- Available with integrated thermostat or preset hygrostat
- DIN-rail (35 mm) clip or screw (M6) fixing
TECHNICAL DATA- Heating element: high-performance cartridge
- Temperature safety cut-out with automatic reset (protects against overheating if fan fails)
- Heater body: extruded aluminium profile
- Axial fan, ball bearing — airflow 160 m³/h (free flow); fan life approx. 50,000 h at 25°C
- Electrical connection: 2-pole, max. 2.5 mm²; clamping screw with strain relief; torque max. 0.8 Nm
- Casing: plastic, UL94 V-0, black
- Mounting: clip for 35 mm DIN rail (EN 50022) or screw fixing (M6)
- Installation position: horizontal
- Dimensions (W x H x D): 182 x 160 x 99 mm
- Weight: approx. 1.45 kg
- Operating / storage temperature: -45 to +70 °C
- Protection type / protection class: IP20 / II (double insulated)
MODEL / ARTICLE TABLE13051.0-00 | Fan heater with thermostat | 230 VAC, 50/60 Hz | 950 W | 0 to +60°C
13051.0-01 | Fan heater with hygrostat | 230 VAC, 50/60 Hz | 950 W | 65% RH (factory-set)
13059.9-00 | Fan heater with thermostat | 120 VAC, 50/60 Hz | 950 W | +32 to +140°F
NOTES & ORDERINGThe product title indicates 750 W for the CR-130 designation; the listed model variants in the technical table include 950 W units. Verify the exact Art. No. and heating capacity when ordering. Other heating capacities (from 200 W) and thermostat/hygrostat options are available on request.
INSTALLATION & MAINTENANCE- Intended for horizontal installation inside electrical enclosures
- Choose CR-030 for bottom-mounted stationary use; CR-130 suited for wall fixing
- Ensure correct electrical connection and torque for terminals
- Inspect fan and ventilation clearance periodically