PRODUCT OVERVIEWThe S1230 series humidity and temperature controller is designed for electronic distribution cabinets and industrial enclosures. The electronic sensor drives relay outputs to control heater and fan on/off according to ambient temperature and relative humidity, providing reliable environmental control for distribution and control panels.
FEATURES- Adjustable temperature and humidity setpoints
- Optical operating display (LED)
- High switching capacity via relay output
- 35 mm DIN-rail mounting (clip)
- Compact dimensions for tight panel spaces
TECHNICAL DATASwitch temperature differential: 2 K (±1 K tolerance) at 25℃/77℉ (50% RH)
Switch differential (humidity): 4% RH (+1% tolerance) at 25℃/77℉ (50% RH)
Humidity reaction time: approx. 5 s
Contact type: change-over contact (relay)
Contact resistance: <10 mΩ
Service life: NC >50,000 cycles; NO >100,000 cycles
Max. switching capacity (relay output): NC: 240VAC, 6(1)A · NO: 240VAC, 8(1.6)A; NC: 120VAC, 6(1)A · NO: 120VAC, 8(1.6)A; 24VDC, 4A
EMC: acc. to EN 55014-1-2, EN 61000-3-2, EN 61000-3-3
Optical indicator: LED
Connection: 5-pole terminal, clamping torque 0.5 Nm max.; rigid wire up to 2.5 mm²; stranded wire (with ferrule) up to 1.5 mm²
Mounting: clip for 35 mm DIN rail, EN6075 or for exit filter EF 118 Series
Casing: plastic according to UL94 V-0, light grey
Dimensions: 77 x 60 x 43 mm
Weight: Approx. 0.20 g
Fitting position: variable
Operating / Storage temperature: 0 to +60℃ (+32 to +140℉) / -20 to +80℃ (-4 to +176℉)
Protection type: IP20
VARIANTSArt.No. S1230.0-00 — Operating voltage: 230VAC, 50/60Hz — Setting range temperature: 0 to +60℃ — Setting range humidity: 50 to 90% RH
Art.No. S1230.9-00 — Operating voltage: 120VAC, 50/60Hz — Setting range temperature: +32 to +140℉ — Setting range humidity: 50 to 90% RH
Art.No. S1230.9-01 — Operating voltage: 230VAC, 50/60Hz — Setting range temperature: 0 to +60℃ — Setting range humidity: 50 to 90% RH
SPECIFICATIONS- Measurement: temperature and relative humidity
- Temperature switching differential: 2 K (±1 K at 25℃)
- Humidity switching differential: 4% RH (±1% at 25℃)
- Humidity response time: approx. 5 s
- Switch output: change-over relay contact, high switching capacity (see values above)
- Contact resistance: <10 mΩ
- Relay life: NC >50,000 cycles; NO >100,000 cycles
- Connection: 5-pole terminal, max. clamping torque 0.5 Nm
- Mounting: 35 mm DIN-rail clip (EN6075)
- Casing material: plastic UL94 V-0, light grey
- Dimensions (W x H x D): 77 x 60 x 43 mm
- Weight: approx. 0.20 g
- Operating temperature: 0 to +60℃; Storage: -20 to +80℃