Three-phase protection relay LXPRF
under-voltagephase sequencephase loss

three-phase protection relay
three-phase protection relay
Add to favorites
Compare this product
 

Characteristics

Measured/monitored value
under-voltage, phase sequence, phase loss
Network
three-phase
Mounting
DIN rail
Trigger voltage

Min.: 77 V

Max.: 520 V

Description

LXPRF - Under voltage monitoring - Monitors own three phase, 3-wire supply - Detects incorrect phase sequence and phase loss - Fixed Trip levels and Time delay - SPDT Relay output - 17.5mm wide, DIN Rail mount - UL Listed The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present, the phase sequence correct and the phase to phase voltages above the fixed trip level. If any of these conditions are not met, the relay will de-energise. Specification - Monitoring function: Under voltage - Monitored supply voltage*: 77 – 143V, 161 – 300V, or 280 – 520VAC - Under trip level: See min. working voltage - Hysteresis: ≈2% - Time delay: ≈ 100ms - Output: SPDT 8A @ 250V (AC1) - Dimensions(mm): W:17.5 x H:89 x D:66.5

Catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.