Summary- Sub-D surge protector
- For RS232, RS485, 4-20mA lines
- 9-pin connector
- Instant deployment
- Secondary protection
OverviewThe DD9ESD surge protectors are designed to protect sensitive terminals connected to data lines equipped with Sub-D connectors. To ensure full compatibility with the lines, all connector contacts are transmitted and protected.
Electrical propertiesNetwork: RS232, RS485, 4-20mA
Nominal line voltage: 24 Vdc
Maximum DC operating voltage (Uc): 40 Vdc
Maximum frequency: > 10 MHz
Maximum data rate: < 40 Mbps
Insertion loss: < 1 dB
Maximum line current @25°C (IL): 750 mA
Maximum discharge current (Imax) - max withstand in 8/20 µs wave per pole: 125 A
Rated discharge current (In) C2 (1.2/50µs / 8/20µs), 10 applications X-X (Line/Line): 125 A
Rated discharge current (In) C2 (1.2/50µs / 8/20µs), 10 applications X-C (Line/Earth): 125 A
Total maximum discharge current (Imax Total) - total max withstand in 8/20 µs wave: 1125 A
Line inductance (± 10 %): none
Protection mode(s): Common mode
Protection level Up (C3 10/1000µs), Y-Y (Line/Line): 130 V
Protection level Up (C3 10/1000µs), Y-C (Line/Earth): 65 V
Line resistance: < 0.05 Ohm
Capacitance @1MHz, X-C (Line/Earth): < 500 pF
Mechanical propertiesTechnology: Clamping diode
Surge protector configuration: 9 wires
Connection: D-Sub 9 pts male/female in input/output
Format: Stacked D-Sub connector
Mounting: On cable
Enclosure material: Thermoplastic UL94 V-0
Operating temperature (Tu): -40 / +85 °C
Protection rating: IP20
Outdoor use: No
Fail-safe disconnection: Short-circuit - transmission interruption - fault mode 2
End-of-life indicator: Transmission interruption
Remote signalling: No
Pinout: all wires transmitted and protected
Dimensions: See drawing
Weight: 0.063 kg
Standards & certificationsCompliance: IEC 61643-21 / NF EN 61643-21 / UL497B
Certification: UL 497B
SchematicsSchematics and illustrations available (product drawing references).
Characteristics / technical specifications- Model reference: DD9-24V
- Part number: 6147
- Brand: CITEL
- Product type: Sub-D surge protector for data lines
- Supported networks: RS232, RS485, 4-20mA
- Nominal line voltage: 24 Vdc
- Maximum DC operating voltage (Uc): 40 Vdc
- Maximum frequency: > 10 MHz
- Maximum data rate: < 40 Mbps
- Insertion loss: < 1 dB
- Maximum line current @25°C: 750 mA
- Maximum discharge current per pole (8/20 µs): 125 A
- Rated discharge current In C2 X-X: 125 A
- Rated discharge current In C2 X-C: 125 A
- Total maximum discharge current (8/20 µs): 1125 A
- Protection mode: Common mode
- Protection level Up (Line/Line): 130 V
- Protection level Up (Line/Earth): 65 V
- Line resistance: < 0.05 Ohm
- Capacitance (1 MHz, X-C): < 500 pF
- Technology: Clamping diode
- Configuration: 9 wires
- Connection: D-Sub 9 pts male/female input/output
- Mounting: On cable
- Enclosure material: Thermoplastic UL94 V-0
- Operating temperature: -40 to +85 °C
- Protection rating: IP20
- Outdoor use: No
- Fail-safe disconnection: Short-circuit - transmission interruption - fault mode 2
- End-of-life indicator: Transmission interruption
- Remote signalling: No
- Pinout: all wires transmitted and protected
- Weight: 0.063 kg
- Standards: IEC 61643-21 / NF EN 61643-21 / UL497B
- Certification: UL 497B