Characteristics

Fluid
air/water
Material
stainless steel
Other characteristics
compact, outdoor, IP55
Applications
for enclosure air conditioning, for electrical cabinet
Power

Min.: 750 W
(2,559.11 BTU/h)

Max.: 25,000 W
(85,303.5 BTU/h)

Temperature

Min.: 1 °C
(34 °F)

Max.: 70 °C
(158 °F)

Description

Overview
The CNW (Watherm) air-to-water heat exchanger is designed to cool electrical enclosures using chilled water circuits (from a centralized plant or Cosmotec chillers). It is suitable where multiple units are installed in the same system and offers an F-GAS-compliant alternative to refrigerant-based air conditioners. Units are tested to EN 1397 and incorporate eco-friendly fans compliant with Regulation 2024/1834. CE and UL Listed certifications are available.

Main performance and ranges
  • Cooling capacity: 750 – 25,000 W
  • Power supply options: 24 Vdc, 230 Vac, 115 Vac, 400/460 Vac
  • Water temperature operability: down to +1°C (without glycol)
  • External ambient operating range: +1°C to +70°C
  • Indoor air temperature range: +10°C to +55°C
  • Protection class: IP55 (also available Type 12 / Type 4 / Type 4X)


Why choose CNW Watherm
  • High cooling capacity with compact dimensions
  • No heat emissions into the environment (heat is rejected to water circuit)
  • Suitable for aggressive or temperature-influenced environments
  • Reduced maintenance and low noise levels


Installation & mounting
Watherm exchangers can be installed internally or externally on electrical cabinets, making them ideal where minimizing enclosure footprint is important. Drilling templates are compatible across CNW05/10/15 and Compact Protherm CNx04/07/10 air conditioners. Two integrated mounting inserts facilitate positioning and installation.

Available versions (control options)
  • Control 0 — Without any control system: water circulates continuously; for applications where no regulation is required.
  • Control 1 — Mechanical thermostat control: internal temperature control via mechanical thermostat managing a solenoid valve.
  • Control 8 — Electronic controller (XCB) with advanced functions: electronic controller, solenoid valve, level indicator, remote monitoring and many auxiliary functions (detailed below).


Control 8 (electronic board) — additional functions
  • Unit status and alarm display
  • Alarm contact (exchangeable NO/NC) and remote/door-open contact
  • Leakage detection for excessive condensation or hydraulic circuit failure
  • Continuous remote monitoring via RS485 and Modbus RTU protocol
  • Hot-spot elimination and possibility to read internal cabinet temperature via remote probe
  • System redundancy and sequencing for two-exchanger communication (alternation or backup)
  • SEM/SEM2 fan-limiting functions to reduce energy consumption at low temperatures
  • Drain residual water by forcing valve open (maintenance/transport)
  • Parameter view and modification from the display, including °C/°F selection and test mode for start-up checks


Model range / example performances & dimensions
  • CNW05 / CNW10 — 800 W – 1,450 W @ 200 l/h; AxLxP 570x280x120 (CNW05) up to 570x280x160 (CNW10 ranges listed)
  • CNW15 — 1,500 W – 1,700 W @ 200 l/h; AxLxP 570x280x160
  • CNW30 — 3,100 W @ 400 l/h; AxLxP 920x400x160
  • CNW50 — 5,300 W / 4,600 W @ 400 l/h; AxLxP 1100x500x240
  • CNW A0 — 11,500 W @ 1000 l/h; AxLxP 1600x590x240
  • CNW A5 / CNWB5 — 16,000 W / 26,000 W @ 2000 l/h; L x W x H 1900x790x350


Hydraulics, connections and options
  • Hydraulic connections: GAS F and NPT threading (if UL) or hose port/mini-valve (accessory)
  • IN/OUT icons engraved on the surface for clear installation
  • Options & accessories: cabinet colour or stainless steel units, various hydraulic connection accessories and customized configurations


Ease of installation & maintenance
  • Two integrated mounting inserts for quick positioning
  • Mechanical thermostat accessible from rear panel without removing enclosure parts
  • Quick-connect connectors for main power, signals and voltage switching (400 V / 460 V)
  • Front-panel removal enables easy maintenance and component inspection without extra side clearance
  • Compact dimensions and new drilling templates for cabinets widths 300 / 400 / 500 / 600 / 800 mm


Standards & certifications
Tested according to EN 1397. Fans compliant with Regulation 2024/1834. Compliant solution in view of F-GAS Regulation 573/2024 restrictions. CE and UL Listed certifications are available to facilitate market access.

Documentation
Product brochure (downloadable brochure in EN available).

Characteristics / technical specifications
  • Product family: Watherm (CNW series)
  • Cooling capacity range: 750 – 25,000 W
  • Power supplies: 24 Vdc, 230 Vac, 115 Vac, 400/460 Vac
  • Water operating temperature: down to +1°C (no glycol required)
  • Ambient operating range (external): +1°C to +70°C
  • Indoor air temp. operating range: +10°C to +55°C
  • Protection rating: IP55 (also Type 12 / 4 / 4X variants)
  • Standards: EN 1397
  • Compliance: Regulation 2024/1834 (fans), F-GAS Regulation 573/2024 considerations
  • Certifications: CE, UL Listed
  • Control versions: Control 0, Control 1 (mechanical thermostat), Control 8 (electronic controller XCB with Modbus RTU via RS485)
  • Control 8 features: alarm contacts, remote/door contact, leakage detection, remote monitoring, hot-spot probe input, sequencing/redundancy, SEM/SEM2 energy-saving functions
  • Hydraulic connections: GAS F, NPT (UL), hose port / mini-valve (accessory)
  • Mounting: wall / cabinet internal or external mounting; drilling templates compatible across CNW05/10/15 and CNx04/07/10
  • Maintenance: front-panel removable for easy access; integrated mounting inserts