The X1-NIS-RLO/EM-03 electro-magnetic relay module is suitable for switching safety related circuits, up to SIL 3 level, for high risk industries. It provides isolation between input coils and output contacts, making available a safety NO contact for Normally De-energized (ND) or Fire & Gas (F&G) loads. A wide compatibility towards different DCS/PLC is guaranteed: driving pulse testing is permitted by a dedicated internal circuit, which prevents contact and LED flickering, while offering an acceptable resistance to the DO Card. To ease maintenance operations, field devices can be disconnected through a two-position insertion/extraction mechanism. This product requires a dedicated Termination Board.SIL 3 / SC 3Installation in Zone 2 / Division 2Loop disconnection to ease maintenance operationsUp to 2 A functional / 6 A inrush currentCompatible with DCS/PLC pulse testingThree port isolation, Input/Output/SupplyTechnical Specifications:Power Dissipation: 0.4 W @ 24 Vdc System In, with 2 A load current, typical.System In: Voltage: 24 Vdc nom (21.5 to 30 Vdc). Current Consumption: 15 mA @ 24 Vdc, typical. Input impedance: 1.6 kΩ @ 24 Vdc, typical.Field Supply: Type: AC or DC voltage supply. Voltage range: 0 to 250 Vac, 0 to 110 Vdc.Field Out: Type: ND/F&G load. Max ratings: 2 A 250 Vac 500 VA, 2 A 110 Vdc 100 W (resistive load). Max inrush current: 6 A. Operate / release time: ≤ 30 / 30 ms.Isolation: Test Voltage: System In/Field Out 2.5 kV.Environmental conditions: Operating temperature: –40 to +60 °C. Storage temperature: –45 to +80 °C.Mounting: Type: On custom Termination Board. Mix only with electro-mechanical relays (X1-NIS-RLO/EM), input relays (X1-NIS-RLI) or pass-through modules (X1-NIS-PAS).Weight: about 50 g.Dimensions: Width 10 mm, Depth 80 mm, Height 120 mm.Channels: 1