Power cable PV1-F
weather-resistantUV-resistantflame-retardant

Power cable - PV1-F - Guangzhou Yuhong Technology CO., Ltd - weather-resistant / UV-resistant / flame-retardant
Power cable - PV1-F - Guangzhou Yuhong Technology CO., Ltd - weather-resistant / UV-resistant / flame-retardant
Add to favorites
Compare this product

Characteristics

Type
power
Protection
flame-retardant, UV-resistant, weather-resistant
Core material
copper
Applications
outdoor, for solar installations
Number of wire
single-conductor, single-core
Material of the insulation
XLPO-insulated
Nominal voltage

1,500 V

Temperature

Min.: -40 °C
(-40 °F)

Max.: 120 °C
(248 °F)

Cross-section

70 mm²
(0.11 in²)

Description

Product Implementation Specifications
  • NB/T 42073 - 2016
  • 2 Pg 116/08.2007
  • IEC 62930 - 2017 (Rated voltage 1.5kV DC photovoltaic cable, etc.)

Product Description
  • PV1-F 1×70mm² is a DC interconnection solar cable designed for the DC side of photovoltaic systems, suitable for 1.5 kV DC applications using cross-linked polyolefin insulation.
  • Rated for continuous operation with maximum conductor temperatures up to 120°C.
  • Multiple cables may be used in parallel when required by system design.

Technical Specifications and Electrical Performance
  • Construction: Halogen-free, flame-retardant cross-linked polyolefin insulation and weather-resistant outer sheath.
  • Rated DC voltage: up to 1.5 kV (typical for single-core/non-grounded PV systems).
  • AC test voltage capability: AC test pulses up to 3.5 kV (dielectric strength validated by testing).
  • DC test voltage reference (manufacturer test context): examples cited such as 15 kV/5 min in documentation for high-voltage testing.
  • Operating temperature range: -40°C to 120°C (mobile or fixed). Maximum permissible temperature rise in cable trays: ≤ 20°C.
  • Good resistance to UV, ozone, oils and weathering for outdoor longevity.
  • Minimum bending radius: ≥ 4 × cable diameter (to facilitate routing in trays and conduits).

Industry Utilization and Application Value
  • Designed primarily for DC interconnections in photovoltaic arrays: between PV modules, to combiner boxes, and inverter DC input wiring.
  • Appropriate for rooftop and ground-mounted solar farms where outdoor durability, UV/ozone resistance and long service life are required.
  • Intended for use by solar project developers, system integrators, electrical contractors and cable suppliers requiring standardized PV-rated cables.

Product Advantages
  • Structural design uses halogen-free, flame-retardant cross-linked polyolefin for insulation and sheath, reducing fire hazard and improving chemical/ozone resistance.
  • Rated for high DC voltages (1.5 kV) and withstands high AC test voltages (e.g., 3.5 kV), supporting dielectric reliability in PV systems.
  • Wide operating temperature range (-40°C to 120°C) and UV/weather resistance for long-term outdoor performance.
  • Relatively small minimum bending radius (≥ 4× diameter) eases installation in constrained conduits and cable trays.
  • Designed to reduce maintenance frequency and operational risk in outdoor electrical networks.

Product Specifications
Product Model | Specification
PV1-F | Unit: 1.5 - 2.0mm²; 2-core: 1.5 - 10mm²
HT2222 | (listed model variant)
PV-Y.NJ | (listed model variant)

Single-core Cable Comprehensive Data
Specification (mm²) | Insulation Thickness (mm) | Sheath Thickness (mm) | Avg Outer Diameter Lower (mm) | Avg Outer Diameter Upper (mm) | Minimum Bending Radius (mm)
1×1.5 | 0.7 | 0.8 | 5.4 | — | 800
1×2.5 | 0.7 | 0.8 | 5.9 | — | 690
1×4 | 0.7 | 0.8 | 6.6 | — | 580
1×6 | 0.7 | 0.8 | 7.4 | — | 500
1×10 | 0.7 | 0.9 | 8.8 | — | 430
1×16 | 0.7 | 0.8 | 10.1 | — | 420
1×25 | 0.9 | 1.0 | 12.5 | — | 340
1×35 | 0.9 | 1.1 | 14.0 | — | 290
1×50 | 1.0 | 1.2 | 16.3 | — | 270
1×70 | 1.1 | 1.2 | 18.7 | — | 250
1×95 | 1.1 | 1.3 | 20.8 | — | 220
1×120 | 1.2 | 1.3 | 22.8 | — | 210
1×150 | 1.4 | 1.4 | 25.5 | — | 210
1×185 | 1.6 | 1.6 | 28.5 | — | 200
1×240 | 1.7 | 1.7 | 32.1 | — | 200

Multi-core Cable Comprehensive Data
Specification (mm²) | Insulation Thickness (mm) | Sheath Thickness (mm) | Avg Outer Diameter Lower (mm) | Avg Outer Diameter Upper (mm) | Minimum Bending Radius (mm)
2×1.5 | 0.7 | 0.9 | 5.4 | 7.0 | 800
2×2.5 | 0.7 | 0.9 | 5.9 | 7.9 | 690
2×4 | 0.7 | 1.0 | 6.6 | 9.1 | 580
2×6 | 0.7 | 1.1 | 7.4 | 10.3 | 500
2×10 | 0.7 | 1.2 | 8.8 | 12.2 | 430
2×16 | 0.7 | 1.3 | 10.1 | 14.5 | 340
3×1.5 | 0.7 | 1.0 | 7.7 | 8.5 | 800
3×2.5 | 0.7 | 1.1 | 8.7 | 9.8 | 690
3×4 | 0.7 | 1.2 | 10.3 | 11.0 | 580
3×6 | 0.7 | 1.2 | 11.1 | 12.3 | 500
3×10 | 0.7 | 1.2 | 13.0 | 14.5 | 430
3×16 | 0.7 | 1.3 | 15.4 | 17.3 | 340
4×1.5 | 0.7 | 1.1 | 8.5 | 9.5 | 800
4×2.5 | 0.7 | 1.2 | 9.8 | 10.7 | 690
4×4 | 0.7 | 1.2 | 11.0 | 12.3 | 580
4×6 | 0.7 | 1.3 | 12.3 | 13.6 | 500
4×10 | 0.7 | 1.4 | 14.5 | 16.1 | 430
4×16 | 0.7 | 1.4 | 17.3 | 19.4 | 340
5×1.5 | 0.7 | 1.2 | 9.5 | — | 800
5×2.5 | 0.7 | 1.2 | 10.7 | — | 690
5×4 | 0.7 | 1.3 | 12.3 | — | 580
5×6 | 0.7 | 1.3 | 13.6 | — | 500
5×10 | 0.7 | 1.4 | 16.1 | — | 430
5×16 | 0.7 | 1.6 | 19.4 | — | 340

Use Scenarios
  • DC interconnection between PV modules, combiner boxes and inverter DC inputs in grid-connected and off-grid solar systems.
  • Rooftop-mounted and ground-mounted solar farms requiring durable outdoor-rated cabling.
  • Installations where compliance to PV-rated standards and long-term reliability (reduced maintenance) are priorities.

FAQ
  • Materials used: halogen-free, flame-retardant cross-linked polyolefin (insulation and sheath) for fire safety and outdoor durability.
  • Customization: manufacturer indicates potential customization options for industrial demands; standard product referenced is PV1-F 70 mm².
  • Installation notes: maintain minimum bending radius ≥ 4× diameter; observe rated temperature limits and system voltage ratings during installation.

Caractéristiques / spécifications techniques
  • Standards: NB/T 42073-2016; 2 Pg 116/08.2007; IEC 62930-2017.
  • Rated voltage: DC up to 1.5 kV; AC reference U0/U 0.6/1 kV for other variants.
  • Typical AC test voltage: 3.5 kV (manufacturer test pulse examples).
  • DC test voltage (manufacturer test context): examples up to 15 kV/5min.
  • Operating temperature: -40°C to 120°C; cable tray temp rise ≤ 20°C.
  • Minimum bending radius: ≥ 4× cable diameter.
  • Insulation & sheath: halogen-free flame-retardant cross-linked polyolefin.
  • Environmental resistances: UV, ozone, weather, oil, radiation resistance per spec references.
  • Expected service life: ~25 years (application dependent).
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.