video corpo

Communication gateway Anybus ABC3090-A
industrialsecuritycybersecurity

Communication gateway - Anybus ABC3090-A - HMS Networks - industrial / security / cybersecurity
Communication gateway - Anybus ABC3090-A - HMS Networks - industrial / security / cybersecurity
Add to favorites
Compare this product

Characteristics

Type
communication, industrial, security, cybersecurity
Network
serial, RS-232, Modbus TCP, Modbus RTU, EtherCAT, RS-485, Ethernet, ProfiNet, EtherNet/IP
Other characteristics
IP20, DIN rail, 2 port, serial device server, multi-protocol, compact, protocol converter

Description

Overview
The Anybus Communicator Serial Master to Common Ethernet enables connection of RS-232/485 devices to PROFINET, EtherCAT, EtherNet/IP and Modbus TCP control systems. The Communicator provides reliable, secure and high-speed data transfer between disparate industrial networks and includes built-in cybersecurity features and an intuitive web-based user interface for configuration and monitoring.

Features and benefits
  • Easily convert proprietary RS-232/485 protocols: Convert Request/Response or Produce/Consume protocols using a drag-and-drop frame builder to create frames, insert/extract data and handle variable frames.
  • Connect up to 32 Modbus RTU servers (slaves): Supports up to 32 servers, 150 Modbus commands, selectable 3 ms serial update rate, graphical transaction builder, controller/PLC triggers and inter-node data exchange.
  • High data throughput: Transfer up to 1500 bytes to and from the controller (network dependent) in each direction (3000 bytes total) via dual 10/100 Mbit full-duplex RJ45 ports with integrated switch for daisy-chaining.
  • Selectable Industrial Ethernet network: Supports EtherNet/IP, EtherCAT, Modbus TCP and PROFINET. Firmware for desired protocols can be installed via the Communicator interface.
  • Instant data transfer: Processing time is minimal; total transfer time equals the cycle times of the connected networks.
  • Configure via web interface over Ethernet: Graphical, responsive web UI with a dedicated Ethernet configuration port; no separate software required.
  • Diagnostics and monitoring: UI displays connection status, enables serial traffic analysis and data monitoring. Includes Live List and Data Exchange Control for node monitoring and control.
  • Drop-in replacement: Legacy mode allows import of Communicator Classic serial configurations to preserve existing controller/PLC setups.
  • Security: Secure boot, physical configuration lock switch, role-based access control and HTTPS configuration to support CRA and industrial security requirements.
  • Industrial design: Industrial-grade components, verified to industry standards, 5-year warranty, slim DIN-rail form factor with front-facing ports and cable tie option for easy installation.

Additional product notes
  • Designed for factory-floor and industrial environments; built to operate reliably under typical industrial conditions.
  • Includes diagnostic tools in the web UI to monitor serial traffic and network exchanges.

Technical specifications
  • Content of delivery: Gateway, power connector, start-up guide, compliance information sheet.
  • Item number: ABC3090-A.
  • Brand: Anybus.
  • Model code: 40-SER-ETH-B.
  • Country of origin: Sweden.
  • Net width: 27 mm.
  • Net height: 144 mm.
  • Net depth: 98 mm.
  • Net weight: 150 g.
  • Packed width: 35 mm.
  • Packed height: 170 mm.
  • Packed depth: 115 mm.
  • Packed weight: 185 g.
  • Mounting: DIN-rail (EN 50022 standard).
  • Current consumption (typical): 90 mA @ 24 V DC (2.2 W).
  • Current consumption (max): 125 mA @ 24 V DC (3 W).
  • Input voltage: 12–30 V DC.
  • Power connector: 3-pin, 5.08 Phoenix plug connector.
  • Reverse polarity protection: Yes.
  • Short circuit protection: Yes.
  • Isolation: True (isolated interfaces).
  • Operating temperature: -25 °C to 70 °C.
  • Storage temperature: -40 °C to 85 °C.
  • Housing materials: PC ABS, UL 94 V0.
  • Packaging material: Cardboard.
  • Warranty: 5 years.
  • Protection class: IP20.
  • UL information: E214107: Ord.Loc UL 61010-1, CSA C22.2 No. 61010-1, UL 61010-2-201, CSA C22.2 No. 61010-2-201.
  • EMC / Environment: EN 55016-2-3 Class A, EN 55032 Class A, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6.
  • WEEE category: IT and telecommunications equipment.
  • Product certifications: CE, UL, KC, WEEE, EMC.
  • Baud rates (serial): 1200, 1800, 2400, 4800, 7200, 9600, 14400, 19200, 35700, 38400, 57600, 115200, 128000 bit/s.
  • Max stations / nodes (serial): 31 (Modbus-RTU / serial nodes).
  • Serial connector: 1x 7-pin, 5.08 Phoenix plug connector (plus configuration port and RJ45 ports).
  • Modbus-RTU mode: Client / Master. Supports standard Modbus RTU Master, custom request/response and produce/consume transactions, trigger initiated transactions, selectable data bits, parity and stop bits.
  • Modbus-TCP mode: Slave / Server. Supports Modbus specification V1.1b3; up to 4 connections; Daisy chaining.
  • Modbus-TCP input/output data size: 1500 bytes.
  • PROFINET mode: Slave. PROFINET input/output data size: 1024 bytes. Conformance class: Class B. Supports RT and daisy chaining.
  • EtherNet/IP mode: Adapter / Slave. EtherNet/IP input/output data size: 1448 bytes. Bandwidth: 10/100 Mbit down to 1 ms cycle time. Supports Ethernet/IP Class 1 and 3, Quick Connect Class B, DLR (beacon mode) and daisy chaining.
  • EtherCAT mode: Slave / SubDevice. EtherCAT input/output data size: 1486 bytes. Bandwidth: 10/100 Mbit down to 100 µs cycle time. ESI available.
  • Modbus-RTU functions supported: 1,2,3,4,5,6,7,8,11,12,15,16,17,20,21,22,24 (and additional functions where listed).
  • Power and protection features: factory reset push button; reverse polarity and short-circuit protection.

Catalogs

No catalogs are available for this product.

See all of HMS Networks‘s catalogs

Other HMS Networks products

Anybus

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.