Analog I/O module MPNC020
digitalCANopenModbus

analog I/O module
analog I/O module
Add to favorites
Compare this product
 

Characteristics

Signal type
digital, analog
Bus
Modbus RTU, Modbus, CANopen
Applications
PLC, temperature, current
Number of inputs/outputs
16 digital inputs, 16 digital outputs
Other characteristics
relay

Description

The MPNC020 module has digital inputs/outputs and it can be used as extension of PLC (TPAC) / operator panels (TP) and any other panel that has a Modbus RTU or CANopen communication protocol. Depending on the communication interface it is necessary to add a "head" to communicate with panel: MPNC010 for CANopen protocol and MPNC006 for Modbus protocol. Up to 16 analog and digital modules can be added in the same line. The MPNC020 is available with: 16 Digital inputs (PNP 0-24Vdc) 16 Digital outputs (PNP 0-24Vdc). See ACIN01 product for relay outputs. Features Digital inputs: (PNP 0-24Vdc) Digital otputs: (PNP 0-24Vdc) Max current for every output: 500mA Max current for all outputs: 2A Power supply: 24Vdc ±15%, 3W Dimensions: 115(l)x115(h)x(22.5mm depht) Working temperature: 0-50°C Protection: IP20