Gas-insulated substation CZBTD
mobilepower distributionfor high-voltage transformers

Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 2
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 3
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 4
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 5
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 6
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 7
Gas-insulated substation - CZBTD - Ningbo Tianan (Group) CO.,Ltd. - mobile / power distribution / for high-voltage transformers - image - 8
Add to favorites
Compare this product

Characteristics

Technology
mobile, gas-insulated
Fonction
power distribution, for high-voltage transformers, handling
Options and accessories
prefabricated, modular, vehicle-mounted
Rated voltage

33 kV, 35 kV, 66 kV, 110 kV, 132 kV

Current

Max.: 3,150 A

Min.: 630 A

Description

General Ningbo Tian'an developed a prefabricated vehicle-mounted mobile substation (model CZBTD) based on domestic and international conditions and exported China's first mobile substation in 2008.

Detailed introduction The CZBTD substation is designed to immediately replace all or part of an existing conventional substation in emergency situations and to restore power. It can be deployed during peak load periods to supplement insufficient supply capacity and used as a temporary substation where permanent construction is delayed or interrupted.

Structure features
  • Full substation functionality: on arrival at site only input and output cables generally need to be connected for rapid commissioning.
  • Modular arrangement: HV section, main transformer and LV switch chamber; HV main switch example ZF10-145 (L). Equipment can be installed on one or multiple semi-trailers with HV components typically placed at the trailer rear for incoming connections.
  • Transport protection: shock-absorption mats between equipment and base frame, temporary support bars for cantilever structures, flexible joints for primary circuit connections and plug-socket secondary connections to reduce on-site assembly and testing.
  • Onboard equipment: primary and secondary winches with rainproof covers, movable ladder for operator and maintenance access, exterior/interior and emergency lighting, fire protection devices.
  • LV switch chamber: three-layer thermal insulation, air-conditioning controlled by season, sealed storage batteries for DC supply, all secondary wiring fixed on top cabinet.
  • Protection and earthing: enclosure protection IP23 with natural ventilation doors open and up to IP43 with doors closed; continuous copper earthing busbar along trailer with at least two independent earthing points at each end and M12 bolts; integrated automatic substation protection equipment.

Technical parameters
Main transformer capacity: 5, 7.5, 10, 15, 20, 25, 31.5, 40, 50 MVA
HV rated voltage: 33, 35, 66, 110, 132 kV
HV rated current: 630, 1250, 1600, 2000 A
HV short-circuit breaking current: 25, 31.5, 40 kA
LV rated voltage: 6.6, 11, 13.8, 22, 33, 35 kV
LV rated current: 1250, 2000, 2500, 3150 A
LV short-circuit breaking current: 20, 25, 31.5, 40 kA
Rated frequency: 50/60 Hz
Ambient temperature: -40 ~ +60 °C
Solar radiation: 1000 W/m2
Humidity: ≤95%
Altitude: ≤2000 m
Wind speed: up to 40 m/s
Seismic (horizontal / vertical): general area 0.15 g / 0.075 g; strong earthquake area 0.3 g / 0.15 g

Typical scheme
Schemes available: circuit breaker scheme and HGIS scheme (schematic diagrams and illustrative images provided in product documentation and description images).

Characteristics / technical specifications
  • Model/series: CZBTD vehicle-mounted mobile substation.
  • Main transformer options: 5–50 MVA.
  • HV: rated voltages 33–132 kV; rated currents up to 2000 A; short-circuit breaking currents 25–40 kA.
  • LV: rated voltages 6.6–35 kV; rated currents up to 3150 A; short-circuit breaking currents 20–40 kA.
  • Frequency: 50/60 Hz. Operating ambient temperature: -40 to +60 °C. Altitude ≤2000 m; humidity ≤95%.
  • Protection grades: IP23 (doors open) / IP43 (doors closed).
  • Transport and maintenance features: shock absorption, flexible primary connections, plug-socket secondary connections, winches, movable ladder and continuous copper earthing busbar.