GeneralThe MNS low-voltage switchgear is a modular combination-type switchgear assembled from standardized components. It is suitable for power plants, substations, petrochemical plants, metallurgy and steel rolling, light textile industries, other industrial enterprises, residential areas and high-rise buildings. It is intended for AC distribution systems (50–60 Hz) with rated working voltages up to 690 V for power distribution, motor control centers, capacitor compensation and related low-voltage applications.
Advantages- Standardized, modular electrical design providing high flexibility.
- Configurable protection levels (IP30–IP54) to suit working and environmental requirements.
- Support for fixed and withdrawable functional units in the same enclosure.
- Compact layout that optimizes internal space.
- Economic distribution-circuit layout and high installation density.
- Possible back-to-back arrangement of units.
- Facilitates equipment upgrades and retrofits.
- High operational reliability and continuity.
- Designed to ensure operator safety.
Standards- IEC 61439-2 Low-voltage switchgear and controlgear
- GB/T 7251.12 Low-voltage switchgear and controlgear
- GB/T 24274 Low-voltage withdrawable switchgear and controlgear
Type and meaningType and identification information illustrate series/type distinctions, module and drawer arrangements to help specify the required configuration and functional layout.
Service conditions- a. Installation position: Indoor installation as complete electrical equipment. With IP54 configuration, operation in other conditions is permitted.
- b. Ambient temperature and relative humidity: Maximum ambient temperature 40 °C (24 h average ≤ 35 °C); minimum −5 °C. Above these limits the equipment must operate at reduced capacity. Clean air; relative humidity ≤ 50% at 40 °C (higher humidity allowable at lower temperatures, e.g. 90% at 20 °C). If condensation may occur, provide ventilation or heating to prevent it.
- c. Altitude: Installation altitude up to 2000 m. Above 2000 m the equipment must be derated.
Main technical parametersElectrical parameters:
Rated insulation voltage Ui: AC 690 V / 1000 V
Rated working voltage Ue: AC 400 V / 690 V
Rated impulse withstand voltage Uimp: 8 kV / 12 kV
1-minute power frequency withstand voltage: 2.5 kV / 3.5 kV
Rated frequency: 50 Hz / 60 Hz
Busbar ratings:
Main busbar rated current Ie: up to 6300 A; rated peak withstand current Ipk: up to 220 kA; rated short-time withstand current Icw: up to 100 kA
Vertical busbar rated current Ie: up to 1250 A; Ipk up to 143 kA; Icw up to 65 kA
Structural features (typical dimensions): Height 2200 mm; widths 400, 600, 800, 1000, 1200 mm; depths 600, 800, 1000, 1200 mm; module pitch E = 25 mm; internal separation up to form 4b; protection levels IP30, IP40, IP42, IP54.
Characteristics / specifications- Series name: MNS
- Rated insulation voltage (Ui): AC 690 V / 1000 V
- Rated working voltage (Ue): AC 400 V / 690 V
- Rated frequency: 50 Hz / 60 Hz
- Main busbar rated current: up to 6300 A
- Main busbar peak withstand current: up to 220 kA
- Main busbar short-time withstand current: up to 100 kA
- Vertical busbar rated current: up to 1250 A
- Vertical busbar peak withstand current: up to 143 kA
- Vertical busbar short-time withstand current: up to 65 kA
- Dimensions (H x W x D mm): 2200 x (400, 600, 800, 1000, 1200) x (600, 800, 1000, 1200)
- Module pitch: E = 25 mm
- Internal separation form: up to 4b
- Protection levels available: IP30, IP40, IP42, IP54
- Ambient temperature range: −5 °C to +40 °C (24 h average ≤ +35 °C)
- Maximum installation altitude: 2000 m (derate above)