GeneralThe XGTD8-12 indoor nitrogen (N2) gas-insulated metal-clad switchgear is an advanced 12 kV electrical assembly filled with environmentally friendlier gas insulation. It is designed for reliable operation in compact secondary transmission and distribution installations, offering a modular, maintenance-reduced solution with long service life and wide environmental adaptability.
Detail introductionThe primary live parts and main circuit are sealed within welded stainless-steel gas tanks and a metal-clad enclosure, protecting against external influences. The modular design supports common-tank and extended-unit layouts, allowing flexible combinations of load switch units, circuit breaker units, metering units and bus PTs to match varied schemes and space constraints.
StandardsIEC62271-200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kV up to 52 kV.
EN50181: Insertion bushings for equipment rated 1 kV to 52 kV and currents 250 A to 2500 A.
GB/T3906, GB/T11022, DL/T404, GB/T1984, GB/T1985, GB/T20840, GB/T11032 (as applicable).
Service Conditions- Ambient temperature: -45°C to +50°C; daily average ≤ 35°C.
- Altitude: ≤ 4000 m (pressure adjustment recommended above 1000 m).
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90%.
- Seismic intensity: not exceed grade 8.
- Environment: free of corrosive or flammable gases and heavy pollution.
Technical parameter (key table items)Rated voltage: 12 kV
Rated current: CB unit 630/1250 A; Load switch unit 630 A
Rated frequency: 50/60 Hz
1 min power-frequency withstand voltage (phase-phase/phase-earth, kV rms): 42; insulation distance: 48
Rated lightning impulse withstand voltage (peak, kV): 75; insulation distance: 85
Auxiliary circuit withstand voltage (kV): 2
Rated short-circuit breaking current (kA rms): 20/25
Rated short-circuit making current (kA peak): 50/63
Rated short-time withstand current (4 s, kA): 20/25
Main circuit resistance per phase (µΩ): ≤160
N2 gas rated operating pressure (MPa): 0.02
Mechanical life: CB/Load switch: 10000 operations; Three-position switch: 5000 operations
Internal arc (IAC) rating: 25/1 (kA/s)
Annual N2 leak rate: ≤0.1%
Protection degrees: IP67 (gas-filled compartment), IP4X (other compartments).
Product Features and Structure- Eco-friendlier insulation: nitrogen (N2) or dry air plus vacuum arc-extinction where applicable; avoids SF6 emissions and enables high material recyclability.
- Safety and reliability: micro-positive gas pressure to limit leakage and maintain functional insulation under partial loss of pressure.
- Modular and compact design: supports load switch, circuit breaker (CB), metering (M) units and bus PT units with fully insulated, fully shielded bus connections for multiple combinations.
- Fully sealed design: primary live parts and main bus enclosed in welded stainless-steel gas tanks; DIN47636-compliant bushings; gas tank protection IP67.
- Front-access operation: user interface and cable connections at front; clear operating instructions; three-position switch visible through inspection window.
- Reduced footprint and maintenance: gas insulation retains compact size and lowers life-cycle maintenance requirements.
- High environmental adaptability: suitable for high altitude, cold, humid, salt-mist and polluted environments.
Product structure and functional compartmentsSecondary meter compartment: for ammeter, voltmeter, protection devices and centralized secondary terminals.
Live display: indicates live cable input/output status.
Gas-pressure gauge: displays safe pressure range; optional alarm contact for low-pressure interlock.
Operation switchgear: provides switch status indications and printed operating instructions.
Gas tank compartment: welded stainless-steel sealed design with IP67 protection.
Pressure relief compartment: for cable and CT installation and as an arc-pressure relief path to cable trench.
Cable compartment front door: removable access to cable compartment; compartment connections via inner-cone side or outer-cone top depending on configuration.
Operation- Preparation: use specified handle; confirm cable compartment front door installation and correct HV cable and secondary circuit connections.
- Power-on: ensure CB/load switch is open; move three-position switch through earthing-open → open → isolation → closing sequence as per instructions; charge mechanism and close CB/load switch by closing knob. Mechanical interlocks prevent incorrect sequences.
- Power-off: rotate closing knob to open CB/load switch; move three-position switch from isolation closed to open with handle.
- Inspection: after confirming cable compartment de-energized, move three-position switch and open front door for inspection per procedure.
Interlock logic- Cable compartment front door can open only when earthing switch is closed and CB/load switch is open.
- Earthing switch cannot be operated when front door is open.
- Isolation and earthing switches cannot be operated when CB/load switch is in closing position.
- CB/load switch cannot be operated when isolation or earthing switches are being operated into forbidden positions.
- Cable compartment front door can be closed only when CB/load switch is in closing position.
Technical specifications- Model: XGTD8-12
- Rated voltage: 12 kV
- Rated current: 630/1250 A (configurations) ; 630 A for certain units
- Rated frequency: 50/60 Hz
- 1 min power-frequency withstand voltage: 42 kV
- Lightning impulse withstand voltage (peak): 75 kV
- Rated short-circuit breaking current: 20/25 kA
- Rated short-circuit making current (peak): 50/63 kA
- Rated short-time withstand current (4 s): 20/25 kA
- Main circuit resistance per phase: ≤160 µΩ
- N2 gas rated operating pressure: 0.02 MPa
- Mechanical life: CB/Load switch 10000 operations; Three-position switch 5000 operations
- Internal arc (IAC) rating: 25/1 (kA/s)
- Annual N2 leak rate: ≤0.1%
- Protection degree: IP67 (gas compartment); IP4X (others)