GeneralThe LZZBJ9-35D indoor single-phase epoxy resin casting current transformer is a fully enclosed epoxy-cast unit. It is resistant to pollution and moisture, compact and lightweight, and can be installed in any orientation.
ApplicationDesigned for power systems with rated frequency 50 or 60 Hz and rated voltage up to 35 kV for indoor installation. Typical uses: electric energy metering, current measurement and relay protection. Commonly applied in air-insulated switchgear and distribution panels rated 6–35 kV.
Standards- IEC 61869-1 (Instrument transformers — General requirements)
- IEC 61869-2 (Instrument transformers — Requirements for current transformers)
- GB 311.1-1997 (Insulation and coordination of high-voltage transmission and transformation equipment)
- GB 5583-1985 (Partial discharge measurement of instrument transformers)
- GB/T 22071.1-2008 (Instrument transformer test guidelines — Part 1: Current transformers)
- JJG 1021-2007 (Electrical transformer verification regulations)
Service conditions- Ambient temperature: +40 °C max, -5 °C min; daily average ≤ 30 °C
- Altitude: ≤ 1000 m
- Negligible effects of direct solar radiation (indoor use)
- Atmosphere free of obvious dust, smoke, corrosive gases, steam or salt
- Humidity: 24 h average relative humidity ≤ 95%; 24 h average vapor pressure ≤ 2.2 kPa; monthly averages: relative humidity ≤ 90%, vapor pressure ≤ 1.8 kPa
Technical data- Rated insulation level: 40.5 / 95 / 185 kV
- Rated frequency: 50 Hz or 60 Hz
- Rated secondary current: 5 A or 1 A
Performance / Rating table (summary)Rated primary current (A) | Accuracy class combinations | Accuracy class & rated output | Short-time thermal current (kA/s) | Rated dynamic current (kA) | Typical weight (kg)
20–100 | 0.2(S), 0.5(S), 0.5, 5P20, 5P25, 5P30 (various combos) | Outputs example: 0.2(S)/0.5(S)/5P | 25–30 (example values) | 30–140 (depends on config) | varies by configuration
150 | accuracy combos as above | output examples: 25–30 | 1 | 63 | varies
200–250 / 300–500 / 600–800 / 1000–3150 | accuracy examples: 31.5 etc. | outputs and short-time thermal currents per table | short-time thermal currents: 1–4 kA/s | dynamic currents up to 80 kA | varies
Appearance and installation sizeTechnical drawing and installation dimensions are provided on the product page or datasheet; consult drawings for mounting details.
Characteristics / technical specifications- Model: LZZBJ9-35D
- Type: Indoor single-phase epoxy resin-cast current transformer (fully enclosed)
- Insulation level: 40.5 / 95 / 185 kV
- Rated frequency: 50 / 60 Hz
- Rated secondary current: 5 A or 1 A
- Rated primary current ranges (examples): 20–100 A; 150 A; 200–250 A; 300–500 A; 600–800 A; 1000–3150 A
- Typical applications: energy metering, current measurement, relay protection in air-insulated switchgear (6–35 kV)
- Environmental limits: ambient temperature -5 °C to +40 °C; altitude ≤ 1000 m; humidity/vapor pressure limits as stated
- Standards: IEC 61869 series, GB standards, GB/T 22071.1, JJG 1021
- Note: For parameters or ratings outside the listed ranges, customization and technical discussion are available with the manufacturer/supplier