GeneralThe JDXF-35 is a single-phase oil-immersed grounding voltage transformer designed for voltage measurement, energy metering and relay protection in 35 kV power systems with ineffectively grounded neutral points, operating at 50/60 Hz.
Type designationSingle-phase oil-immersed voltage transformer, model JDXF-35.
Service condition- Installation altitude: less than 1000 m above sea level
- Ambient temperature: -40°C to +40°C
- Intended for outdoor installation
StructureThe transformer is a single-phase, three-winding unit with a column iron core. The assembly is mounted on the cover inside a square oil tank. HV and LV windings are led out separately through respective insulators. The HV insulator is fitted with an oil conservator on top; the primary terminal (A-side) is located on the conservator. The oil tank and insulators are filled with transformer oil providing paper-oil insulation. An oil-resistant rubber diaphragm isolates the conservator from air. The conservator is equipped with an oil level indicator. An oil drain valve is provided at the bottom of the tank and mounting holes are available on the tank baseboard.
Technical data- Standards: IEC and GB1207-2006
- Rated primary voltage: 35000/√3 V (35 kV system)
- Rated secondary voltage: 115/√3 V
- Residual winding rated voltage: 100/3 V
- Rated voltage factor/time: 1.9 for 8 h
- Maximum output: 1500 VA
- Primary winding power-frequency withstand voltage: 95 kV for 60 s (graded insulation may allow frequency-doubling test as alternative)
- Lightning impulse withstand: full wave 185 kV; chopped wave 220 kV
- Power-frequency test voltage (N terminal ↔ secondary and ground): 5 kV for 60 s
- Power-frequency test voltage (between secondary windings and secondary ↔ ground): 3 kV for 60 s
- Continuous operation permitted up to 1.2 times rated primary voltage
Outline dimension drawingOutline and mounting dimensions are provided in the product drawings and technical documentation on the product page.
Characteristics / Technical specifications- Type: Single-phase oil-immersed grounding voltage transformer
- Winding configuration: Three-winding (primary, secondary, residual)
- Core: Column iron core
- Insulation: Paper-oil insulation, oil-filled tank and insulators
- Oil conservator: With oil level indicator and oil-resistant rubber diaphragm
- Protection/features: Oil drain valve, baseboard mounting holes
- Frequency: 50 Hz / 60 Hz
- Rated primary voltage: 35000/√3 V
- Rated secondary voltage: 115/√3 V
- Residual winding rated voltage: 100/3 V
- Rated voltage factor/time: 1.9 for 8 h
- Maximum output: 1500 VA
- Altitude/temperature limits: <1000 m; -40°C to +40°C
- Intended use: Outdoor measurement and relay protection in ineffectively grounded 35 kV systems