Vacuum load-break switch FTD9-12D
AChigh-voltagethree-phase

Vacuum load-break switch - FTD9-12D - Ningbo Tianan (Group) CO.,Ltd. - AC / high-voltage / three-phase
Vacuum load-break switch - FTD9-12D - Ningbo Tianan (Group) CO.,Ltd. - AC / high-voltage / three-phase
Vacuum load-break switch - FTD9-12D - Ningbo Tianan (Group) CO.,Ltd. - AC / high-voltage / three-phase - image - 2
Vacuum load-break switch - FTD9-12D - Ningbo Tianan (Group) CO.,Ltd. - AC / high-voltage / three-phase - image - 3
Add to favorites
Compare this product

Characteristics

Type
vacuum
Electrical characteristics
short-circuit, AC, three-phase, high-voltage
Operating mode
high-voltage
Applications
distribution, for substations
Number of poles
3-pole
Other characteristics
indoor
Primary current

630 A

VAC

12 kV

Description

General
The FTD9-12D indoor high-voltage AC vacuum load switch is an indoor switchgear device able to close, open and carry normal operating currents (including specified overloads) as well as abnormal currents (e.g. short-circuit currents). It is designed for three-phase AC 50/60 Hz, 12 kV systems and is used with complete distribution equipment, ring network switchgear and modular substations. Its layout, technical characteristics, appearance and dimensions correspond to the VTD9-12D vacuum circuit breaker, making it suitable for installation in small or constrained spaces.

Quality standard
IEC62271-103 High-voltage switchgear and control equipment - Part 103: 1 kV~52 kV AC load switches
IEC62271-105 High-voltage switchgear and control equipment - Part 105: 1 kV~52 kV AC load switch-fuse combinations
GB/T3804 High-voltage AC load switches 3.6 kV ~ 40.5 kV
GB/T16926 High-voltage AC load switch - fuse combination device

Service Conditions
  • Ambient temperature: -25°C ~ +40°C
  • Altitude: ≤ 1000 m
  • Relative humidity: daily average ≤ 95%
  • Monthly average relative humidity ≤ 90%
  • Daily average vapor pressure ≤ 2.2×10⁻³ MPa
  • Monthly average vapor pressure ≤ 1.8×10⁻³ MPa
  • Seismic level: seismic intensity ≤ 8
  • Applicable location: free from dripping water, flammable/explosive hazards, chemically corrosive gases and severe vibrations


Technical Data
Item — Unit — Parameter
Rated frequency — Hz — 50/60
Rated voltage — kV — 12
Rated power-frequency withstand voltage (1 minute, r.m.s) — kV — phase-to-phase and phase-to-ground: 42
Isolation fracture — kV — 48
Control and auxiliary circuits — kV — 2
Rated lightning impulse withstand voltage (peak) — kV — phase-to-phase and phase-to-ground: 75; isolation fracture: 85
Rated current — A — 630
Rated short-time withstand current and time — kA/s — 20/4
Rated peak withstand current — kA — 50
Rated handover (transfer) current — A — 1
Mechanical life — operations — 5000
Main circuit resistance per phase — mΩ — ≤ 100
Clearance between open contacts — mm — 9 ± 1
Contact travel — mm — 5.5 ± 1
Contact closing bounce time — ms — ≤ 2
Three-phase asynchronous closing/opening — ms — ≤ 2
Average opening speed (contact just opened - 6 mm) — m/s — 0.9 - 1.3
Average closing speed (6 mm - contact just opened) — m/s — 0.4 - 0.8
Rated contact pressure — N — 1000 ± 100

Technical characteristics
  • Reasoned design and novel structure: operating mechanism integrated with five-prevention interlocking; modular components (sealed pole, earthing switch) combined on a common mounting frame.
  • Integrated indicators: operating panel indicators combined with primary circuit indicators for clear, simple status display and rational interlocking to prevent incorrect operations.
  • Miniaturization: smaller volume compared with air-insulated switches of same specification; cabinet width down to 500 mm.
  • Reduced maintenance: maintenance-free vacuum arc-extinguishing chambers (poles) ensure long service life and low operating costs.
  • Visual consistency: VTD9 circuit breaker, FTD9 load switch and GTD isolating switch share identical external dimensions to facilitate extension and cabinet combination.


Typical outline dimensions and structural notes
Outline drawings available for FTD9-12/630 and FTD9-12D/630 indicate inter-phase distance P = 210 and support normal and reversible installations.

Characteristics / technical specifications
  • Model: FTD9-12D
  • Application: three-phase AC 50/60 Hz systems (distribution ring panels, modular substations)
  • Rated frequency: 50/60 Hz
  • Rated voltage: 12 kV
  • One-minute power-frequency withstand voltage (phase-phase/phase-ground): 42 kV
  • Isolation fracture: 48 kV
  • Lightning impulse withstand voltage (phase-phase/phase-ground): 75 kV (isolation fracture 85 kV)
  • Rated current: 630 A
  • Main circuit resistance (per phase): ≤ 100 mΩ
  • Short-time withstand current/time: 20 kA / 4 s
  • Peak withstand current: 50 kA
  • Mechanical life: 5000 operations
  • Open contact clearance: 9 ± 1 mm
  • Contact travel: 5.5 ± 1 mm
  • Rated contact pressure: 1000 ± 100 N