GeneralThe FTD9-12D indoor high-voltage AC vacuum load switch is an indoor switchgear device able to close, open and carry normal operating currents (including specified overloads) as well as abnormal currents (e.g. short-circuit currents). It is designed for three-phase AC 50/60 Hz, 12 kV systems and is used with complete distribution equipment, ring network switchgear and modular substations. Its layout, technical characteristics, appearance and dimensions correspond to the VTD9-12D vacuum circuit breaker, making it suitable for installation in small or constrained spaces.
Quality standardIEC62271-103 High-voltage switchgear and control equipment - Part 103: 1 kV~52 kV AC load switches
IEC62271-105 High-voltage switchgear and control equipment - Part 105: 1 kV~52 kV AC load switch-fuse combinations
GB/T3804 High-voltage AC load switches 3.6 kV ~ 40.5 kV
GB/T16926 High-voltage AC load switch - fuse combination device
Service Conditions- Ambient temperature: -25°C ~ +40°C
- Altitude: ≤ 1000 m
- Relative humidity: daily average ≤ 95%
- Monthly average relative humidity ≤ 90%
- Daily average vapor pressure ≤ 2.2×10⁻³ MPa
- Monthly average vapor pressure ≤ 1.8×10⁻³ MPa
- Seismic level: seismic intensity ≤ 8
- Applicable location: free from dripping water, flammable/explosive hazards, chemically corrosive gases and severe vibrations
Technical DataItem — Unit — Parameter
Rated frequency — Hz — 50/60
Rated voltage — kV — 12
Rated power-frequency withstand voltage (1 minute, r.m.s) — kV — phase-to-phase and phase-to-ground: 42
Isolation fracture — kV — 48
Control and auxiliary circuits — kV — 2
Rated lightning impulse withstand voltage (peak) — kV — phase-to-phase and phase-to-ground: 75; isolation fracture: 85
Rated current — A — 630
Rated short-time withstand current and time — kA/s — 20/4
Rated peak withstand current — kA — 50
Rated handover (transfer) current — A — 1
Mechanical life — operations — 5000
Main circuit resistance per phase — mΩ — ≤ 100
Clearance between open contacts — mm — 9 ± 1
Contact travel — mm — 5.5 ± 1
Contact closing bounce time — ms — ≤ 2
Three-phase asynchronous closing/opening — ms — ≤ 2
Average opening speed (contact just opened - 6 mm) — m/s — 0.9 - 1.3
Average closing speed (6 mm - contact just opened) — m/s — 0.4 - 0.8
Rated contact pressure — N — 1000 ± 100
Technical characteristics- Reasoned design and novel structure: operating mechanism integrated with five-prevention interlocking; modular components (sealed pole, earthing switch) combined on a common mounting frame.
- Integrated indicators: operating panel indicators combined with primary circuit indicators for clear, simple status display and rational interlocking to prevent incorrect operations.
- Miniaturization: smaller volume compared with air-insulated switches of same specification; cabinet width down to 500 mm.
- Reduced maintenance: maintenance-free vacuum arc-extinguishing chambers (poles) ensure long service life and low operating costs.
- Visual consistency: VTD9 circuit breaker, FTD9 load switch and GTD isolating switch share identical external dimensions to facilitate extension and cabinet combination.
Typical outline dimensions and structural notesOutline drawings available for FTD9-12/630 and FTD9-12D/630 indicate inter-phase distance P = 210 and support normal and reversible installations.
Characteristics / technical specifications- Model: FTD9-12D
- Application: three-phase AC 50/60 Hz systems (distribution ring panels, modular substations)
- Rated frequency: 50/60 Hz
- Rated voltage: 12 kV
- One-minute power-frequency withstand voltage (phase-phase/phase-ground): 42 kV
- Isolation fracture: 48 kV
- Lightning impulse withstand voltage (phase-phase/phase-ground): 75 kV (isolation fracture 85 kV)
- Rated current: 630 A
- Main circuit resistance (per phase): ≤ 100 mΩ
- Short-time withstand current/time: 20 kA / 4 s
- Peak withstand current: 50 kA
- Mechanical life: 5000 operations
- Open contact clearance: 9 ± 1 mm
- Contact travel: 5.5 ± 1 mm
- Rated contact pressure: 1000 ± 100 N