GeneralThe FTD9-12RD indoor AC vacuum load switch‑fuse combination apparatus integrates three‑pole vacuum load switches with three fuses fitted with impactors. Activation of any impactor causes all three poles of the load switch to open simultaneously. The vacuum load switch (arc‑extinguishing chamber) and the fuse are connected in series: the vacuum switch performs closing/opening of load and overload currents, while the fuse handles short‑circuit interruption.
Detailed introductionDesigned for three‑phase AC 50/60 Hz, 12 kV distribution systems, the FTD9-12RD is intended for indoor distribution switchgear, ring main units and modular substations. Its layout, technical characteristics, appearance and dimensions are largely equivalent to the FTD9-12D vacuum load switch, making it suitable for installations with limited space.
Quality standard- GB/T16926 — High voltage AC load switch‑fuse combination device
- NB/T10283 — Guidelines for testing high voltage AC load switch‑fuse combination electrical appliances
- IEC 62271-105 — High‑voltage switchgear and controlgear — Part 105: AC load switch‑fuse combinations (1 kV–52 kV)
Service Conditions- Ambient temperature: -25°C to +40°C
- Altitude: ≤ 1000 m
- Relative humidity: daily average ≤ 95%, monthly average ≤ 90%
- Daily average vapor pressure ≤ 2.2 × 10⁻³ MPa; monthly average ≤ 1.8 × 10⁻³ MPa
- Seismic grade: intensity ≤ 8
- Installation site: no dripping water, no flammable/explosive atmosphere, no chemically corrosive gases, and no severe vibration
Technical DataRated frequency (Hz): 50/60
Rated voltage (kV): 12
Power frequency withstand voltage (1 min, r.m.s) phase‑to‑phase / phase‑to‑ground (kV): 42
Insulation breakdown (kV): 48
Control and auxiliary circuits (kV): 2
Rated lightning impulse withstand voltage (peak) phase‑to‑phase / phase‑to‑ground (kV): 75
Insulation breakdown (impulse) (kV): 85
Rated current (A): depends on selected fuse
Rated short‑circuit breaking current (r.m.s) (kA): depends on selected fuse
Rated transfer (handover) current (A): 3150
Mechanical life (operations): 5000
Main circuit resistance per phase (mΩ): ≤ 250
Clearance between open contacts (mm): 9 ± 1
Contact travel (mm): 5.5 ± 1
Three‑phase asynchronous opening/closing (ms): ≤ 2
Average opening speed (contact just opened -6 mm) (m/s): 0.9–1.3
Rated contact pressure (N): 1000 ± 100
Typical outline dimensions and structural diagramOutline drawings are available for FTD9-12R and FTD9-12RD (inter‑phase distance P = 210). Diagrams show upright orientation; inverted installation is also permissible.
Characteristics / Technical specifications- Model: FTD9-12RD
- Application: Three‑phase AC 50/60 Hz, 12 kV distribution systems
- Rated voltage: 12 kV
- Rated frequency: 50/60 Hz
- Power frequency withstand voltage (1 min, r.m.s): 42 kV
- Lightning impulse withstand voltage (peak): 75 kV
- Rated current and breaking capability: depend on selected fuse
- Rated transfer current: 3150 A
- Mechanical life: 5000 operations
- Main circuit resistance per phase: ≤ 250 mΩ
- Clearance between open contacts: 9 ± 1 mm
- Contact travel: 5.5 ± 1 mm
- Three‑phase asynchronous opening/closing: ≤ 2 ms
- Average opening speed: 0.9–1.3 m/s
- Rated contact pressure: 1000 ± 100 N