GeneralThe GTD9-12D indoor high-voltage AC isolating switch provides specified insulation distance and clear visible disconnection between contacts in the open position. In the closed position it conducts normal circuit currents and can withstand specified abnormal currents for the required duration; it also permits opening and closing under no-load conditions (including small inductive or capacitive currents).
Detail introductionSuitable for three-phase AC 50/60 Hz systems with rated voltage 12 kV. Designed to safely isolate circuits for maintenance, repair or testing, protecting personnel and equipment. Layout, appearance and dimensions are compatible with VTD9-12D and FTD9-12D vacuum switches. Typical through-wall/wall-mounted isolating switch, easy to combine and expand within switchgear assemblies.
Standards- IEC62271-1: High voltage switchgear and control equipment - Part 1: Common technical requirements for AC switchgear and control equipment
- IEC62271-102: High voltage switchgear and control equipment - Part 102: AC isolating switches and grounding switches
- GB/T1985: High voltage AC isolating switch and grounding switch
- GB/T11022: Common technical requirements for high voltage switchgear and control equipment standards
- DL/T486: High voltage AC isolating switch and grounding switch
Service Conditions- Environmental temperature: -25°C to +40°C
- Altitude: ≤ 1000 m
- Relative humidity: daily average ≤ 95%; monthly average ≤ 90%
- Daily average vapor pressure ≤ 2.2×10⁻³ MPa; monthly average ≤ 1.8×10⁻³ MPa
- Seismic grade: seismic intensity ≤ 8
- Applicable location: free from dripping water, flammable/explosive hazards, chemically corrosive gases and severe vibration
Technical DataRated frequency | Hz | 50/60
Rated voltage | kV | 12
Rated power frequency withstand voltage (1 min, r.m.s) - phase to phase and phase to ground | kV | 42
Isolation fracture (power frequency) | kV | 48
Control and auxiliary circuits | kV | 2
Rated lightning impulse withstand voltage (peak) - phase to phase and phase to ground | kV | 75
Isolation fracture (lightning) | kV | 85
Rated current | A | 630, 1250
Rated short-time withstand current and time | kA/s | 20/4, 25/4, 31.5/4
Rated peak withstand current | kA | 50, 63, 80
Mechanical life | Times | 3000
Main circuit resistance of each phase | mΩ | ≤45, ≤40
Clearance between open contacts | mm | 125 ± 1
Typical outline dimensions and structural notesInter-phase distance P = 210 mm. Product can be installed upright or inverted. Typical rated short-time withstand current (kA, 4 s) = 25 for common variants. Rated current options: 630 A or 1250 A.
Characteristics / technical specifications- Model: GTD9-12D
- Application: indoor three-phase AC systems, no-load operation
- Rated frequency: 50/60 Hz
- Rated voltage: 12 kV
- Rated power frequency withstand voltage (1 min, r.m.s): 42 kV (phase-phase and phase-ground)
- Rated lightning impulse withstand voltage (peak): 75 kV; isolation fracture 85 kV
- Rated short-time withstand current (4 s): options 20 kA, 25 kA, 31.5 kA
- Rated peak withstand current: 50, 63, 80 kA
- Main circuit resistance per phase: ≤45 mΩ or ≤40 mΩ (variant dependent)
- Clearance between open contacts: 125 ± 1 mm
- Inter-phase distance: 210 mm
- Mechanical life: 3000 operations