DescriptionMDM7000-LP is a smart differential pressure transmitter equipped with a remote diaphragm seal system, designed to measure differential pressure for monitoring liquid level, gas level, density, pressure and gas flow in general and harsh process environments. The transmitter integrates a monocrystalline silicon piezoresistive sensor and offers configurable output options for remote monitoring and control.
Advantages- Accuracy: ±0.75%
- Measurement range: 0.4 bar – 2.5 bar
- Long-term stability: ±0.1% Span / 10 years
- Monocrystalline silicon piezoresistive sensor for stable performance
- High-overload protection diaphragm to improve overload resistance
- Approvals for vessel installation: DNV, ABS, KR, NK, RS
Features (key technical values)- Model: MDM7000-LP
- Sensor technology: Monocrystalline silicon piezoresistive sensor
- Measured variables: Differential pressure for liquid level, gas level, density, pressure and gas flow
- Range: 0.4 bar – 2.5 bar
- Accuracy: ±0.75% (plus effects from diaphragm seal system)
- Turn-down ratio: 100:1
- Long-term stability: ±0.1% Span per 10 years
- Ambient temperature effect: (0.375 + 0.125 TD)% / 10°C in range -20°C to 80°C
- Supply voltage range: 18.3 V – 44 V DC (voltage effect ≤ ±0.005%/V)
- Vibration tolerance: ≤ 0.1% Span (GB/T18271.3 / IEC61298-3)
- Output signals: 4–20 mA DC; HART; RS485-Modbus (configurable)
- Ingress protection: IP66 / IP67
- Weight: approx. 6.35 kg (housing only)
- Diaphragm: High-overload protection diaphragm
- Approvals / certificates: DNV, ABS, KR, NK, RS; additional certificates available (CSA, IECEx, ATEX, NEPSI, CE)
Industry application- Petroleum / Oil & Gas
- Chemical industry
- Power generation
- Steel industry
- Cement
- Pulp & paper
- Food & beverage
- Medical & health
- Water engineering
- General process industries
Technical specifications- Model: MDM7000-LP
- Sensor: Monocrystalline silicon piezoresistive sensor
- Measured variable: Differential pressure (liquid/gas level, density, pressure, gas flow)
- Range: 0.4–2.5 bar
- Accuracy: ±0.75% (+ diaphragm seal system effects)
- Turn-down: 100:1
- Long-term stability: ±0.1% Span / 10 years
- Outputs: 4–20 mA DC; HART; RS485-Modbus
- Supply voltage: 18.3–44 V DC
- Operating temperature: -20°C to 80°C (see temperature effect)
- Vibration: ≤ 0.1% Span (GB/T18271.3 / IEC61298-3)
- Ingress protection: IP66 / IP67
- Weight: ~6.35 kg (body)
- Diaphragm: High-overload protection
- Certifications: DNV, ABS, KR, NK, RS; optional CSA, IECEx, ATEX, NEPSI, CE